Bulletin 71.4:63EG-98HM
December 2014
D102628X012
www.fisherregulators.com
Type 63EG-98HM Pilot-Operated Relief Valve or
Backpressure Regulator
W6866
Figure 1. Type 63EG-98HM Pilot-Operated Relief Valve or
Backpressure Regulator
Introduction
The Type 63EG-98HM can be used for gas, liquid
or steam applications. For applications up to 550°F /
288°C, the Type 63EG-98HM utilizes high temperature
Ethylenepropylene (EPR) or Per uoroelastomer (FFKM)
for Class VI shutoff. If used in a corrosive service,
Per uoroelastomer (FFKM) and other elastomers are
available options that offer superior resistance to heat and
most corrosive chemicals.
When using the Type 63EG-98HM with a corrosive liquid,
usually water or a water-containing solution, the valve
materials must be selected with care. For aqueous solutions,
use a Stainless steel linear cage or Whisper Trim™ III Cage
and body ange to ensure valve plug travel on a corrosion-
free surface.
The Type 63EG-98HM is not an ASME certi ed device.
Features
• Variety of Construction Materials—WCC steel and
CF8M Stainless steel are standard constructions.
Alloy 20, Hastelloy
®
C and Monel
®
are available options
upon request.
• Low Build-up Capability—Minimal build-up pressure is
required for main valve to achieve wide-open ow.
• Chemically Compatible Elastomers—
Per uoroelastomer (FFKM) is available for corrosive
chemical applications.
• No Assembly Adjustments Required—Precise
machining ensures that the main valve plug shuts off at
both the port and upper seals at the same time.
• Fast Speed of Response—High gain piloting system for
faster response than standard piloting system.
• Excellent Overpressure Protection—Superior pump
bypass regulator for overpressure protection in pump
recirculation applications.
• NACE Availability—Optional materials available for
applications handling sour gases. These constructions
comply with recommendations of the NACE International
standards MR0175 and/or MR0103.
• Tight Shutoff—Elastomer seats for Class VI shutoff on
high temperature applications to 550°F / 288°C.
• Easily Converted to Differential Control—The pilot
is ready for differential backpressure control with the
addition of a sealing washer on the adjusting screw.
• Labor-Saving Trim—Main valve body can stay in-line
during maintenance. Tested trim packages can be made
up and stocked ahead of time for fast replacement.
• Versatility in Both Liquid and Gas Service—The
pilot exhaust port and standard tapped pilot spring
case each come with removable vent for remote piping
when necessary. The standard tapped pilot spring case
comes with an optional gasketed closing cap that permits
pressure loading for remote pneumatic adjustment of the
set pressure. For remote upstream registration, the pilot
supply tubing may be disconnected at the 1/4 NPT main
valve body tapping and this tapping plugged.
Hastelloy
®
C is a mark owned by Haynes International, Inc.
Monel
®
is a mark owned by Special Metals Corporation