026-1710 Rev 1 05-15-07
CH Breaker Gateway
Installation and
Operation Manual
Przeglądanie stron 0
1 2 3 4 5 6 ... 21 22

Podsumowanie treści

Strona 1 - Operation Manual

026-1710 Rev 1 05-15-07CH Breaker GatewayInstallation andOperation Manual

Strona 2

4 • CH Breaker Gateway I&O Manual 026-1710 Rev 1 05-15-074.1.3. Setting the NET SwitchesThe PRC100MOD controller has a pair of switches that, when

Strona 3

REFLECS Site Controller Software Setup • 54.2.3. Setting the RS485 I/O Termi-nation JumpersAs part of a site controller’s RS485 I/O (COM A or COM D) N

Strona 4

6 • CH Breaker Gateway I&O Manual 026-1710 Rev 1 05-15-075.2.2. Adding Lighting Schedule Appli-cationsFor each group of breakers to be controlled

Strona 5 - Table of Contents

CH Breaker Gateway (HHT) Software Setup • 75. Set Proof Type to ON Only. If the light circuit is read as open when it should normal-ly be closed, the

Strona 6

8 • CH Breaker Gateway I&O Manual 026-1710 Rev 1 05-15-076.1.1. HHT ScreensThe Home screen is the first screen that appears. Press F1 at any time

Strona 7 - 2 Mounting

Mapping Breaker Numbers to Board and Points (Bd:Pt) Charts/Appendices • 96.1.3. StatusFrom the Option screen, select 1 for Status. The Status screen s

Strona 8 - 3 Power Wiring

10 • CH Breaker Gateway I&O Manual 026-1710 Rev 1 05-15-077.2. 8RO Mapping TableTable 7-2 shows how the outputs of the 8RO Board are connected to

Strona 9 - 4 Networking

Appendix A: WorksheetsUse the workspace below to assign breakers to groups. Refer to Table A-2 for group number board and point assign-ment.Panel 1 Br

Strona 10

16AI Address = ____ Fill in the Gateway 16AI board address that you set with the HHT. For groups 17-32, add 1; for groups 33-48, add 2.8RO Address =

Strona 11 - 5 Site Controller Soft

33 1 134 2 235 3 336 4 437 5 538 6 639 7 740 8 841 9 142 10 243 11 344 12 445 13 546 14 647 15 748 16 8Table A-2 - Mapping Group Numbers to Point Numb

Strona 13 - 6 Software Setup

Appendix B: TroubleshootingSYMPTOM POSSIBLE PROBLEM SOLUTIONBoard Offline I/O Network Problems Check wiring polarity. Verify the 485+ uses one color

Strona 14

HHT Home screen displays FAIL: I/O NET. Red Alarm Status LED is blink-ing once per second.I/O Net Status LED is not blink-ing.Communication has been l

Strona 16 - 7.3. 16AI Mapping Table

1640 Airport Road, Suite 104Kennesaw, GA 31044Phone: (770) 425-2724Fax: (770) 425-9319ALL RIGHTS RESERVED.The information contained in this manual has

Strona 18

CH Breaker Gateway and MultiFlex CHB I&O Manual Table of Contents • viTable of Contents1 OVERVIEW ...

Strona 20 - Appendix B: Troubleshooting

The CH Breaker Gateway System Overview • 11 OverviewThe CH Breaker Gateway is designed to allow CPC’s family of site controllers to interface directly

Strona 21

2 • CH Breaker Gateway I&O Manual 026-1710 Rev 1 05-15-07The Gateway should be mounted in an environment with ambient temperature between -40°F an

Strona 22

Connecting the CH Breaker Gateway to the Breaker Panels Networking • 34 Networking4.1. Connecting the CH Breaker Gateway to the Breaker Pan-elsThe Cut