1592025990 XEV22D GB r1.5 14.11.2014.docx XEV22D 6/6
delay
ALARMS
dAo Alarm delay after restarting regulation
0.0 to 42min 00s, res.
10s
10.0 Pr2
tdA Type of alarm signalled by relay ALL; SH; PrE; Di
ALL Pr2
bon Buzzer enabling No; yES n Pr2
tbA Alarm relay silencing No; yES n Pr2
LPL
Lower pressure limit for superheat
regulation (related to PrM parameter)
[PA4 to P20 bar]
[PA4 to P20 psi]
-0.5 Pr2
MoP
Maximum operating pressure threshold
(related to PrM parameter)
[LoP to P20 bar]
[LoP to P20 psi]
11.0 Pr2
LoP
Minimum suction pressure limit (related
to PrM parameter)
[PA4 to MoP bar]
[PA4 to MoP psi]
-0.5 Pr2
PHy Pressure alarm Hysteresis
[0.1 to 5.0 bar]
[1 to 72 psi]
0.2 Pr2
dML delta MoP-LoP 0 to 100% 5 Pr2
MSH Maximum superheat alarm
[LSH to 80.0°C]
[LSH to 176°F]
80.0 Pr2
LSH Lowest superheat alarm
[0.0 to MSH°C]
[0 to MSH°F]
2.5 Pr2
SHY Superheat hysteresis
[0.1 to 25.5°C]
[1 to 77°F]
0,5 Pr2
SHd Superheat alarm activation delay 0 to 255 s 30 Pr2
DISPLAY
Pressure stability index 0-240s 5 Pr2
Temperature stability index 0-240s 3 Pr2
Lod Local display SH; PEr; P1; P2 SH Pr2
CF Temperature measurement units °C; °F °C Pr2
PMu Pressure measurement unit bAr; PSi bAr Pr2
rES Resolution (only °C) dE; in dE Pr2
PrM Type of pressure (Absolute / relative) rEL; AbS rEL Pr2
CLP Cooling call percentage Read only --- Pr1
tP1 Temperature probe value Read only --- Pr1
PPr Pressure probe value Read only --- Pr1
tP2
Temperature converted from pressure
probe
Read only
--- Pr1
SH Super heat value Read only --- Pr1
STH Superheat set point valu Read only --- Pr1
oPP Actual Opening percentage Read only --- Pr1
d1S Free of voltage digital input state Read only --- Pr1
d2S Main voltage digital input state Read only --- Pr1
Adr Serial address 1 to 247 1 Pr2
Mod Modbus type Std; AdU Std Pr2
Ptb Parameters map - - - - Pr2
rEL Release software - - - 1.5 Pr2
Pr2 Second level menu - - - - Pr1
Komentarze do niniejszej Instrukcji