Cryogenic-Rotary Valve
Instruction Manual
Form 5482
February 2005
4
Figure 2. Maximum Pressure/Temperature Ratings
CLASS 150, KEL‐F SEAL CLASS 300, KEL‐F SEAL
C0759-1 / IL
KEL-F
A4132-1 / IL A3715-2 / IL
Preparing for Installation
CAUTION
To avoid damage to the valve disc
during installation, the valve must be
in the fully-closed position. If the Type
A31A Cryogenic valve is equipped with
a fail-open actuator, remove the
actuator before installing the
valve/actuator assembly or cycle the
valve into the fully closed position.
Then, take appropriate steps to ensure
that the actuator does not cause the
valve to open during installation.
1. The Type A31A Cryogenic valve is normally
shipped as part of an assembly with an actuator and
other accessories. If the valve and actuator have
been purchased separately or if the actuator has
been removed for maintenance, properly mount the
actuator and adjust valve/actuator travel and all
travel stops before inserting the valve into the line.
Follow the instructions in this manual for Adjusting
Travel stops. Also, refer to a separate actuator
instruction manual for detailed actuator mounting
and adjustment procedures.
2. If not previously removed, remove the protective
end covers from the valve and inspect the valve
body to be certain that it is free of foreign material.
Also, be certain that adjacent pipelines are free of
any foreign material, such as pipe scale or welding
slag that could damage the valve seating surfaces.