381333–195 A
50 Hanover Road, Florham Park, New Jersey 07932–1591 USA
For sales or service call 1 800 800–2726 (ASCO) www.ascopower.com
ASCO POWER TECHNOLOGIES CANADA PO Box 1238, 17 Airport Road, Brantford, Ontario, Canada N3T 5T3
telephone 519 758–8450, fax 519 758–0876, for service call 1 888 234–2726 (ASCO) www.asco.ca
Operator’s
Manual
7000 Seri es 7ADTB
Automatic Delayed–Transition Transfer
& Bypass–Isolation Switches
H des ig n 600 thro ug h 1200 amp .
DANGER is used in this manual to warn of high
voltages capable of cau si n g shock , burns, or death .
WARNINGisusedinthismanualtowarn
of possible personal injury.
CAUTIONisusedinthismanualtowarn
of possible equipment damage.
600–1200 amp. sizes
Refer to t he outline and wiring drawings provided
with your 7000 Series ADTB for all installation and
connection details and accessories.
Refer to Group 5 Controller U ser’s Guide 381333–126
for ATS status display messages, time delays, pickup
& dropout settings, and adjustments.
An exp erien c ed licensed elec t rician must in stall the
7ADTB.
Rating Label
Each 7000 Series 7ADTB contains a rating label to
define the loads and fault circuit withstand/closing
ratings. Refer to the label on the Transfer Switch for
spec ific values.
Do not exceed the values on the nameplate/
rating label. Exceeding the rating can cause
personal injury or serious equipment damage.
TABLE OF CONTENTS
section-page
INSTALLATION
Mounting 1-1.............................
Power Connections 1-1....................
Engine Starting & Auxiliary Circuits 1-2......
Functional Test 1-2, 1-3, 1-4.................
TESTING & SERVICE
Transfer Test 2-1..........................
Preventive Maintenance 2-1................
Disconnecting the Controller 2-1............
Manual Load Transfer 2-2..................
Trouble-Shooting 2-2......................
BYPASSING & ISOLATING
Bypassing the ATS 3-1, 3-2.................
Isolating the A TS 3-3, 3-4...................
Return to Service 3-5, 3-6, 3-7...............
INDEX back cover.........................
Przeglądanie stron 0
1 2 3 4 5 6 ... 16 17

Podsumowanie treści

Strona 1 - Operator’s

381333–195 A50 Hanover Road, Florham Park, New Jersey 07932–1591 USAFor sales or service call 1 800 800–2726 (ASCO) www.ascopower.comASCO POWER TECHNO

Strona 2 - Phase Poles

SECTION 3 BYPAS SING & ISOLATING3 --- 1Figure 3–1. Status lights and Engine Control.TRANSFER SWITCHCONNECTED TO NORMALCONNECTED TO EMERGENCYLower

Strona 3 - SECTION 1 INSTALLATION

BYPASSING & ISOLATING(continued)3 --- 2To Bypass Normal Source* To Bypass Emergency Source*(Load connected to Normal Source)The Transfer Swit ch C

Strona 4 - Functional Test

BYPASSING & ISOLATING(continued)3 --- 3ISOLATING THE ATSIsolating is required before any servi ce work can beperformed on the automatic transfer s

Strona 5 - INSTALLATION

BYPASSING & ISOLATING(continued)3 --- 44. Open the lower enclosure door. Pull out both left andright side rails then use the twohandles to roll ou

Strona 6

BYPASSING & ISOLATING(continued)3 --- 55. R em o ve the movable con tac t co v er.Useyourthumbandfingerstosqueezethesidesinward until the contact

Strona 7 - In Canada

BYPASSING & ISOLATING(continued)3 --- 6TS CONNECTEDMiddle amber lightshould come on.TS TESTTS ISOLATEDpositionwindowTESTclockwise – draws inthe tr

Strona 8 - TESTING & SERVICE

BYPASSING & ISOLATING(continued)3 --- 7RETURN TO SERVICE continued*This procedure explains how to return the Bypass SwitchHandle to the OPEN posit

Strona 9

INDEXPrinted in U.S.A.Copyright 2007 ASCO Power Technologies, L.P.Aauxiliary circuits, 1–2Bbarriers, interphase, 3–4, 3–5bypassing the ATS, 3–1, 3–2Cc

Strona 10 - BYPASSING THE ATS*

Namepl ateThe Transfer Switch nameplate includes data for eachspecific 7000 Series 7ADTB. Use the switch only within thelimits shown on this nameplate

Strona 11 - BYPASSING & ISOLATING

SECTION 1 INSTALLATION1 --- 1A SCO 7000 Series A utomatic Delayed–TransitionTra nsfer & Bypass–Isolati on Switches (7ADTBs) arefactory wired and t

Strona 12

INSTALLATION (continued)1 --- 2Engine Starting ContactsAll customer connections, including the engine controlcontact connections, are located on termi

Strona 13

INSTALLATION(continued )1 --- 3REDREDGREENGREENobservethese lightsAMBERFigure 1-2. Standard controls and indicators.Functional TestRead all instructio

Strona 14

INSTALLATION (continued)1 --- 4REDREDGREENGREENobservethese lightsAMBERoperatethis switchFigure 1-3. Standard controls and indicators.2 – Electrical O

Strona 15

SECTION 2 TESTING & SERVICE2 --- 1TRANSFER TESTTest the Aut omatic Transfer Switch portion of the 7000Series 7ADTB at least once a month. This pro

Strona 16

TESTING & SERVICE(continued)2 --- 2TROUBLE-SHOOTINGNote any optional accessories that may be furnished onthe 7ADTB and review their operation. Ref

Strona 17 - Printed in U.S.A

TESTING & SERVICE(continued)2 --- 3handleshaftframeUP opens theEmergency sourcecontactsDOWN closes theEmergency sourcecontactsUPPER SHAFTFigure 2–