ROC364 Instruction Manual
B-9 Local Display Panel Rev Jun/05
Table B-6. Analog Input Point Display Parameters
Parameter Description
AI Tag 10-character identifier Tag for the Analog Input.
Units 10-character unit of measurement identifier for the EU Value assigned to the Analog Input.
EU Value in engineering units (EU).
PT# Module rack letter and Point Number of the Analog Input as installed in the ROC.
ALM
Alarm Code is an 8-bit field. If a bit is set to “1”, the alarm is active. If a bit is set to “0,” the alarm
is cleared.
Figure B-11 shows the alarm code bits and the alarms they represent for an Analog Input point.
Alarm Code 0 0 0 0 0 0 0 0
Manual Flag
Scanning Enabled / Disabled
Low Alarm Flag
A-D Failure
Low Low Alarm Flag
Not Used
High Alarm Flag
Rate Alarm Flag
High High Alarm Flag
Figure B-11. Analog Input Alarm Code Bits