10
Leak Detection Kit Installation Scenarios
Scenarios
Upflow
Unit
Detection
around
entire unit
Upflow
Unit
Detection
on sides and
in front of unit
Downflow
Unit
Detection
around
entire unit
Downflow
Unit
Detection
on sides and
in front of unit
Distance from unit
Distance:
In back
On sides
In front
2 ft
2 ft
2 ft
No cable behind
2 ft
2 ft
1 ft
1 ft
6 ft
No cable behind
1 ft
6 ft
Unit
(footprint-in.)
Part number
Challenger
(32.5 x 32.5) LT460-Z30 LT460-Z20 LT460-Z30 LT460-Z25
Himod
(69 x 35) LT460-Z35 LT460-Z20 LT460-Z35 LT460-Z25
Deluxe System/3
(50 x 35) LT460-Z30 LT460-Z20 LT460-Z35 LT460-Z25
(74 x 35) LT460-Z35 LT460-Z20 LT460-Z35 LT460-Z25
(99 x 35) LT460-Z45 LT460-Z25 LT460-Z45 LT460-Z30
(122 x 35) LT460-Z45 LT460-Z25 LT460-Z45 LT460-Z30
DS
(73 x 35) LT460-Z35 LT460-Z20 LT460-Z45 LT460-Z30
(86 x 35) LT460-Z35 LT460-Z20 LT460-Z45 LT460-Z30
(98 x 35) LT460-Z45 LT460-Z25 LT460-Z45 LT460-Z30
(109 x 35) LT460-Z45 LT460-Z25 LT460-Z45 LT460-Z30
(132 x 35) LT460-Z45 LT460-Z25 LT460-Z45 LT460-Z30
6-ft clearance