Emerson Site Manager Przewodnik Instalacji Strona 43

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 130
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 42
Installation Guide AMS Suite: Intelligent Device Manager
NOVEMBER 2013
43
Det-Tronics
The Det-Tronics System Interface is used to monitor fire and gas detectors on the Det-
Tronics Eagle Quantum Premier (EQP) fire and gas Safety System with the S3 software
application
(version 8.6.0.1). To install the this system interface, refer to “Det-
Tronics” on page 106. Refer to Det-Tronics documentation for EQP setup information.
PROFIBUS
The PROFIBUS System Interface lets you use AMS Device Manager to view and
configure PROFIBUS DP or PROFIBUS PA devices connected to a Softing PROFIBUS
Ethernet Gateway or a Softing PROFlusb Modem.
Softing FG-100 and FG-300 Ethernet Gateways are supported. The FG-100 supports
one PROFIBUS segment while the FG-300 supports up to 3 PROFIBUS DP segments.
Each PROFIBUS DP segment can support up to 32 devices.
The Softing PROFlusb Modem is a USB device that can be used as a master in a
PROFIBUS segment. It also offers DP-V0 and DP-V1 capabilities.
Przeglądanie stron 42
1 2 ... 38 39 40 41 42 43 44 45 46 47 48 ... 129 130

Komentarze do niniejszej Instrukcji

Brak uwag