Vission 20/20 Retrofit Instructions
Przeglądanie stron 0
1 2 3 4 5 6 ... 13 14

Podsumowanie treści

Strona 1

Vission 20/20 Retrofit Instructions

Strona 2

10ViSSion® 20/20 Retrofi t Instructions • 35391SCRFStep 2. An auxiliary contact from compressor motor starter is required. Connect isolated contact t

Strona 3 - 1.0 General Information

11ViSSion® 20/20 Retrofi t Instructions • 35391SCRFStep 4. A dry contact from control relay CR12 must be wired to oil pump motor starter coil. This d

Strona 4 - 2.1 Removal

12ViSSion® 20/20 Retrofi t Instructions • 35391SCRFTorque Specifications (ft-lbs)TypeBoltHeadMarkingsNominal Size Numbers or Inches#10 1/4 5/16 3/8 7/1

Strona 6

35391SCRF Rev. 1 (4/13) Emerson and Vilter are trademarks of Emerson Electric Co. or one of its affi liated companies. © 2012 Emerson Climate Technolog

Strona 8

3ViSSion® 20/20 Retrofi t Instructions • 35391SCRFTable of ContentsSections Page1.0 General Information ...

Strona 9

4ViSSion® 20/20 Retrofi t Instructions • 35391SCRF2.0 Vission 20/20 Retrofi t Instructions This procedure defi nes the steps required to replace a Vilt

Strona 10 - #12AWG THHN (MINIMUM)

5ViSSion® 20/20 Retrofi t Instructions • 35391SCRF2.2 InstallationNOTETorque all hardware according to torque table specifi cations, see Table 1.NOTEMod

Strona 11 - CUSTOMER ANALOG WIRING

6ViSSion® 20/20 Retrofi t Instructions • 35391SCRFStep 8. Install hardware to secure new vibration isolators (5) to mounting holes of Vission 20/20 mi

Strona 12

7ViSSion® 20/20 Retrofi t Instructions • 35391SCRFNOTEStainless steel tubing is not provided in a retrofi t kit.Step 10. Route stainless steel tubing f

Strona 13

8ViSSion® 20/20 Retrofi t Instructions • 35391SCRFStep 12. Connect cables (10) to transducers (7).Figure 6. Block and Bleed Assembly with Transduce

Strona 14

9ViSSion® 20/20 Retrofi t Instructions • 35391SCRFCAUTIONDo not route A/C and D/C wires together, this willcause Electromagnetic Interferance. Failure