Installation Drawings
17
Figure 14 Terminal details, Liebert Battery Cabinet
Note:
1. All dimensions are in inches (mm)
2.. 24" minimum clearance above unit required for air exhaust.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable access plates.
5. Control wiring and power wiring must be run in separate conduit.
6. Aluminum and copper-clad aluminum cables are not recommended.
7. All wiring must be in accordance with national and local electrical codes.
1.75
(45)
.56
(14)
1.75 (45)
1.75 (45)
1.75
(45)
1.75
(45)
.53
(14)
See Bus
Termination Detail
Negative Term. Bus (-)
Positive Term. Bus (+)
Top Vie w
Right Side View
Front View
Ground Bus
(See Detail)
* Doors And Covers Removed for Clarity
Ground Bus Detail
+
-
Bus Termination Detail