670 Series Panel-Mounted Loading
Regulator Assemblies
!
WARNING
Fisher
®
regulators should be installed,
operated and maintained in accordance
with federal, state and local codes, rules
and regulations and Emerson Process
Management Regulator Technologies,
Inc. instructions.
If a leak develops in the system, it indicates
that service is required. Failure to take the
regulator out of service immediately may
create a hazardous condition.
Call a gas service person in case of trouble.
Only a qualied person must install or
service the regulator.
Introduction
The 670 Series panel-mounted loading regulator assemblies
are used primarily for manually controlling pressure to
diaphragm control valves or as remote pressure loaders for
pressure-balance gas regulators. They are also widely used
for remote control of gas pressure to burners in renery tube
stills, power plants and similar process furnaces.
Principle of Operation
The 670 Series regulators are set manually to control supply
pressure to diaphragm control valves or gas regulators.
Instrument and manual loading pressures are read from the
pressure gauges of the regulator. If pressure to the valve
needs to be adjusted, the regulator handwheel is turned
clockwise to increase the supply pressure or counterclockwise
to decrease the supply pressure.
Installation
Inspect the panel after it is removed from its packing.
Connect a 1/4 in. / 6.4 mm pipe line from the operating
supply pressure to the connection marked “IN” on the
pressure regulator.
One and two-gauge panels: Connect a line to the diaphragm
casing of the main valve or regulator and run it to the
connection marked “OUT” on the panel regulator. When
installing a two-gauge panel, connect a line from the control
pressure line to the upper diaphragm casing and to the
control pressure gauge (instrument loading pressure) in the
back of the panel (see Figure 2).
Two-gauge panel with a three-way changeover valve:
Connect the air supply, diaphragm connection and
instrument loading pressure line to the panel regulator as
shown in Figure 4.
Overpressure Protection
!
WARNING
Overpressuring any portion of this equipment
may cause damage to regulator parts, leaks
in the regulators or personal injury due to
bursting of pressure-containing parts or
explosion of accumulated gas.
To avoid overpressure, provide appropriate
overpressure protection to ensure that none of
the pressure limits will be exceeded.
The regulator assembly should be inspected for
damage after any overpressure condition.
Figure 1. Typical 670 Series Regulators: Two-Gauge Panel with
Three-Way Changeover Valve
W0554
Przeglądanie stron 0
1 2 3 4

Podsumowanie treści

Strona 1 - Regulator Assemblies

670 SeriesD200109X012Instruction ManualForm 965February 2015www.fisherregulators.com670 Series Panel-Mounted Loading Regulator Assemblies!WARNINGFishe

Strona 2 - 670 Series

670 Series2Table 1. Type Number DescriptionTYPENUMBER OF GAUGEDESCRIPTIONREGULATOR TYPE NUMBERMAXIMUM INLET PRESSUREMAXIMUM OUTLET PRESSUREMAXIMUM EME