5. A clogged spring case vent hole may cause the
regulator to function improperly. To keep this
vent hole from being plugged (and to keep the
spring case from collecting moisture, corrosive
chemicals, or other foreign material) orient the vent
to the lowest possible point on the spring case or
otherwise protect it. Inspect the vent hole regularly
to make sure it is not plugged. Spring case vent
hole orientation may be changed by rotating the
spring case with respect to the body. The 1/4-inch
threaded NPT spring case vent may be remotely
vented by installing tubing or piping into the vent.
6. For regulator shutdown, install upstream block
and vent valves and downstream block and vent
valves (if required), or provide some other suitable
means of properly venting the regulator inlet and
outlet pressures.
7. Apply a good grade of pipe compound to the male
pipe threads before making connections, making sure
not to get the pipe compound inside the regulator.
8. Install tubing tting or piping into the 1/4-inch
threaded NPT inlet connection on the body
(key 1) and into the 1/4-inch threaded NPT body
outlet connection.
9. The second 1/4-inch threaded NPT outlet can be
used for a gauge or other use. If not used, it must
be plugged.
10. When installing a 67CFS Series regulator in
an existing installation, it may be necessary to use
spacers to adapt the installation. If the mounting
bolts are too long, place a spacer on the bolt. To
be sure the regulator is secure, the bolts should
have at least two full threads of engagement.
1. With proper installation completed and
downstream equipment properly adjusted, slowly
open the upstream and downstream shutoff valve
(when used) while using pressure gauges to
monitor pressure.
!
1 Body
2 Drain Valve
3 Flange Screw
4
(1)
O-Ring
5 Dripwell
6
(1)
Filter Element
7 Spring Case
9 Filter Retainer
10
(1, 2)
Valve Cartridge
11
(1, 2)
Valve Plug
12
(1, 2)
Valve Spring
13
(1, 2)
Valve Retainer
14
(1, 2)
O-Ring
15
(1, 2)
Relief Valve Soft Seat
16
(1)
Diaphragm Assembly
17 Spring
18 Adjusting Screw
19 Locknut
20 Upper Spring Seat
23 1/4-Inch Pipe Plug (not shown)
25 Label
26
(1)
Filter Gasket
33 Closing Cap
34 Spacer
37 Thrust Washer
45 Vent Screen
1. Recommended Spare Part
2. Valve cartridge assembly includes keys 10, 11, 12, 13, 14, and 15.
control spring to produce an outlet
2. If outlet pressure adjustment is necessary, monitor
outlet pressure with a gauge during the adjustment
procedure. The regulator is adjusted by loosening
the locknut (key 19), if used, and turning the
adjusting screw or handwheel (key 18) clockwise
to increase or counterclockwise to decrease the
outlet pressure setting. Tighten the locknut to
maintain the adjustment position.