Bulletin 71.1:912N
2
See Table 1
1/4 NPT
1/4 or 3/8 NPT
(1)
250 psig (17,2 bar)
(1)
See Table 1
(1)
20 psig (1,4 bar)
3 psid (0,21 bar differential) above outlet
pressure setting; provide external relief if start-to-
discharge point exceeds 3 psid (0,21 bar differential)
(see Table 1).
0.073 or 0.094-inch (1,9 or 2,4 mm)
4
See Tables 2 and 3
See Table 1
Adequate only for relieving minor
buildup situations such as those caused by chips
or dirt blocking the seat partly open; for major
malfunctions, external relief is required according
to the Overpressure Protection section
(1)
-20° to 160°F (-29° to 71°C)
Internal
1/8 NPT tapped
with removable screen
Constructions Without Handwheel: Over body outlet
Handwheel Constructions: Over body inlet
1.3 pounds (0,6 kg)
Zinc
Zinc
Plated carbon steel
Fluorocarbon (FKM) disk
with zinc lever, stainless steel lever pin and rod, and
plated carbon steel lever screws
Nitrile (NBR)/Nylon (PA)
Plated steel
Plated steel
Plated steel
spring wire, except stainless steel spring wire for
control spring 1L507937022
Stainless steel spring wire
Brass and zinc
Plastic
Brass, zinc, and steel
Composition
304 Stainless Steel
1. The pressure/temperature limits in this Bulletin or any applicable standard limitation should not be exceeded.
downward and the valve disk moves away from the orice.
912N Series regulators include an internal relief valve for
overpressure protection.
The 912N Series have outlet pressure ratings lower than their
inlet pressure ratings. Although the internal relief valve provides
very limited downstream overpressure protection, complete
downstream protection is needed if the actual inlet pressure
exceeds the outlet pressure rating.
Overpressuring any portion of these regulators may cause
leakage, damage to regulator parts, or personal injury due to
bursting of pressure-containing parts or explosion of accumulated
gas. Provide appropriate overpressure protection devices to
ensure that none of the limits found in the Specications section
or Table 1 will be exceeded.
Regulator operation with normal operating limits does not
preclude the possibility of damage from external sources or
from debris in the gas line. A regulator should be inspected for
damage after any overpressure condition.
912N Series regulators may be installed in any position;
however, the spring case vent should be pointed down on
outside installations. If gas escaping through the internal
relief valve could constitute a hazard, the spring case vent
should be piped to a location where escaping gas will not
be hazardous. If the vent will be piped to another location,
obstruction-free tubing should be used and a screened
vent should be installed on the end of the vent pipe. On
all installations, the vent or end of the vent pipe must