1© 2015 Emerson Climate Technologies, Inc.AE4-1287 R8Copeland Discus™ Compressors with Demand Cooling™ SystemAE4-1287 R8 March 2015TABLE OF CONTENTSSe
10© 2015 Emerson Climate Technologies, Inc.AE4-1287 R8DEMAND-COOLINGCONTROL MODULETO CONTROLCIRCUITREFRIGERANT INJECTION LINEMANUAL SHUTOFFVALVEINJECT
11© 2015 Emerson Climate Technologies, Inc.AE4-1287 R8CCL1L2L3L1L2LMLMAASCS2402NOTE: Compressors withinternal overload protectionMUST have some means,
12© 2015 Emerson Climate Technologies, Inc.AE4-1287 R8CCL1L2L3L1L2LMLMAAS2402NOTE: The control circuitmust be arranged so that theDemand Cooling Modul
13© 2015 Emerson Climate Technologies, Inc.AE4-1287 R8ControlCCL1L2L2L1120v240vM2LAInjectionSolenoidTemp.SensorInjector ControlSwitchLMASDemandCooling
14© 2015 Emerson Climate Technologies, Inc.AE4-1287 R8The contents of this publication are presented for informational purposes only and are not to be
15© 2015 Emerson Climate Technologies, Inc.AE4-1287 R8 Copeland® Demand Cooling® Diagnostics Demand Cooling Operating CharacteristicsThe Copeland Dema
16© 2015 Emerson Climate Technologies, Inc.AE4-1287 R8Bench Check of the Module and Injection ValveRequired equipment:• A controlled voltage source
17© 2015 Emerson Climate Technologies, Inc.AE4-1287 R8is closed. If correct control voltage is not present, replace the module.3. If correct control
18© 2015 Emerson Climate Technologies, Inc.AE4-1287 R8Form No. 92-91 R2 (4/09)be occasional Demand Cooling trips. If lowering system temperatures corr
2© 2015 Emerson Climate Technologies, Inc.AE4-1287 R8Safety InstructionsCopeland Discus™ compressors are manufactured according to the latest U.S. and
3© 2015 Emerson Climate Technologies, Inc.AE4-1287 R8ELECTRICAL SHOCK HAZARD• Disconnect and lock out power before servicing. • Discharge all capaci
4© 2015 Emerson Climate Technologies, Inc.AE4-1287 R8IntroductionEnergy effi ciency regulations drive continuous change in the availability of refriger
5© 2015 Emerson Climate Technologies, Inc.AE4-1287 R8Performance data for Demand Cooling compressors includes the effects of injection when it is requ
6© 2015 Emerson Climate Technologies, Inc.AE4-1287 R8C. The alarm signal for local or remote control. The alarm relay is energized, after a one minute
7© 2015 Emerson Climate Technologies, Inc.AE4-1287 R8Figure 1 – Demand Cooling Systemnomenclature beginning with -ADx (e.g. 4DKNF63KL-TSK-AD0) Demand
8© 2015 Emerson Climate Technologies, Inc.AE4-1287 R8Injection lines represent maximum operation point within discharge temperature limits of the comp
9© 2015 Emerson Climate Technologies, Inc.AE4-1287 R8Figure 5 – Standard Location of CoreSense Temperature Probe (for compressors without CoreSense Di