Bulletin 71.1:CP200
5
Principle of Operation
Refer to Figure 3. The CP200 Series has spring-to-
close construction and uses a 67CP Series pressure
loading regulator to supply loading pressure to the top
of the main diaphragm. Adjustment to the downstream
pressure is therefore made by adjusting the loading
pressure regulator. The load pressure supplied by the
loading regulator is constant and equal to the desired
downstream pressure plus the pressure required to
overcome the light closing spring.
Type CP200 Base Regulator
Increasing Downstream Demand
As downstream demand increases the outlet
pressure registering on the underside of the main
diaphragm decreases and the constant loading
pressure above the main diaphragm forces the
diaphragm downward. This downward diaphragm
motion is transferred through the lever causing the
main disk to move away from the orice seating
surface to supply additional ow downstream to the
required demand.
Decreasing Downstream Demand
As downstream demand decreases the outlet
pressure registering on the underside of the main
diaphragm increases forcing the main diaphragm
upward. This upward motion is transferred through
the lever causing the main disk to move toward the
orice seating surface to reduce ow to meet the
required demand.
Zero Downstream Demand (Lockup)
As downstream demand decreases further, the outlet
pressure registering under the main diaphragm
together with the closing spring act to close the
main disk against the orice seating surface. At this
point the loading regulator will continue to supply
a small amount of gas downstream that is equal to
the capacity of the bleed restriction in the diaphragm
assembly. As downstream demand decreases to zero
ow outlet pressure rises to meet the lock-up pressure
of the loading regulator. This causes the loading
regulator to lockup to stop all ow downstream.
Figure 3. Type CP200IN Pressure Loaded Pressure Reducing Regulator with Internal Registration Operational Schematic
M1129
CLOSING SPRING
DIAPHRAGM
CONTROL SPRING
VALVE DISK
ORIFICE
VALVE STEM
LEVER
PRESSURE RETAINING
PLUG (DO NOT REMOVE)
MAIN REGULATOR
TYPE 67CP PRESSURE
LOADING REGULATOR
INLET PRESSURE
OUTLET PRESSURE
ATMOSPHERIC PRESSURE
LOADING PRESSURE