Bulletin 71.1:CS400
11
Installation
The CS400 Series regulators may be installed in any
position. However, the spring case vent should be
pointed downward. If gas escaping through the
CS400 Series internal relief valve could constitute a
hazard, the spring case vent must be piped to a location
where escaping gas will not be hazardous. If the vented
gas will be piped to another location, use obstruction-free
tubing or piping at least equal in size to the vent and the
end of the vent pipe must be protected from anything
that might clog it. Regulators with External Registration
require the use of an external control line.
Downstream Control Line Connection
A CS400 Series regulator with an EN, ET or ER in the
type number has a blocked throat, an O-ring stem seal
and a 3/4 NPT control line tapping in the lower diaphragm
casing, Figure 5. A regulator with a downstream
control line is used for monitoring installations or other
applications where there are other equipment installed
between the regulator and the pressure control point.
The O-ring stem seal helps separate body pressure
from diaphragm case pressure on monitor installations
where leakage cannot be tolerated.

The CS400 Series regulators have outlet pressure
ratings that are lower than their inlet pressure
ratings. A pressure relieving or pressure limiting
device is needed for Types CS400IN, CS400IT,
CP400EN and CS400ET if inlet pressure can exceed
the outlet pressure rating as these regulators do not
have standard internal relief, high outlet pressure
shutoff or integral slam-shut module. Optional
internal relief constructions are available and
denoted by the last letter of the Type Number sufx
and are dened in the following paragraphs.
Overpressuring any portion of a regulator or associated
equipment may cause personal injury, leakage or
property damage due to bursting of pressure-containing
parts or explosion of accumulated gas. Provide
appropriate pressure relieving or pressure limiting
devices to ensure that the limits in the Specications
section are not exceeded. Regulator operation within
ratings does not prevent the possibility of damage from
external sources or from debris in the pipeline.

Type numbers with the “R” sufx, e.g. Type CS400IR,
provide internal relief discharge across the diaphragm
assembly (Figure 4) to minimize overpressure. Any
outlet pressure above the start-to-discharge point of the
non-adjustable relief spring moves the diaphragm off
the relief seat, allowing excess pressure to discharge
through the vent. If emergency conditions should exist
that prevent normal operation of the regulator or internal
relief valve, the relief valve stem acts as a secondary
travel stop contacting the underside of the closing
cap and stopping the upward travel of the relief seat.
Since the diaphragm continues to rise as downstream
pressure builds, the diaphragm lifts off of the relief seat
to provide relief operation. The secondary travel stop for
internal relief is not available on token relieving units.
See Figures 10, 11, 12, 13 and 14 for relief capacity.

Type numbers with the “T” sufx, e.g. Type CS400IT,
provide low capacity/token internal relief. Token relief
provides relief only from minor overpressure caused
by nicks or dents on the orice or disk or by thermal
expansion of gas in the downstream line. Token relief
also provides a token or signal, in the form of odor,
that an overpressure situation is occurring. Start-to-
discharge values of the Token relief are consistent with
the Internal relief values found in Table 4.

Type numbers with the “N” sufx, e.g. Type CS400IN,
do NOT provide internal relief discharge across the
diaphragm assembly.
Integral True-Monitor™ Protection
Types CS403IN, CS403EN, CS403IT and CS403ET
combine the operation of a conventional two-regulator
wide-open monitor set into one body. The Integral True-
Monitor is installed on the inlet side of the body and serves
to throttle ow and maintain an acceptable downstream
pressure in the case where the primary regulator fails
to regulate. Unlike multiple seat designs that rely on the
primary regulator for all protection against loss of pressure
control modes, the CS403 Series provides protection from
a wide variety of conditions that could cause the primary
regulator not to regulate downstream pressure.