CSB400 Series
10
Figure 7. CSB400 Series Regulator Installed with the Vent Pointed Downward and with a
Type 289H Relief Valve for High Capacity Relief
Type CSB403 Integral
True-Monitor™ Operation
Type CSB403 combines the operation of a conventional
two-regulator wide-open monitor set into one body, see
Figure 5. The Integral True-Monitor is installed on the
inlet side of the body and serves to throttle ow and
maintain an acceptable downstream pressure in the
case where the primary regulator ceases to regulate
downstream pressure. During normal operation the
Integral True-Monitor is in a wide-open state as its
setpoint is set higher than the primary regulator. See
Table 7 for guidance regarding the setpoints of the
regulator and associated Integral True-Monitor sets.
If the downstream pressure should rise to the setpoint of
the Internal Monitor due to a loss of pressure control by
the primary regulator, the Integral True-Monitor
will assume control and regulate the ow to the
downstream system. If token relief is present, it will
relieve a small amount of gas to the atmosphere as an
indication that the Integral True-Monitor is controlling the
downstream pressure.
The Type CSB403 provides the option of internal or
external downstream pressure registration. External
registration requires a downstream sensing line. See
Figure 9 for guidance regarding installation of the
downstream control line. Refer to the Type TM600
Instruction Manual for additional details of Integral
True-Monitor operation.
Type CSB404 Slam-shut Operation
The Type VSX4 slam-shut module on the Type CSB404
regulator is a fast acting shut-off device that provides
overpressure (OPSO) or over and underpressure
(OPSO / UPSO) protection by completely shutting off the
ow of gas to the downstream system. See Table 8 for
guidance regarding the typical setpoints of the regulator
and associated slam-shut OPSO and also the combined
OPSO and UPSO setpoints. The Type VSX4’s actions
are independent of the Type CSB404 regulator and of
variations to the inlet pressure. The Type VSX4 comes
standard with external downstream pressure registration,
with the option for internal registration only on the Rp 1
x 2-1/4 GAZ body. External registration requires a
downstream sensing line. See Figure 10 for guidance
regarding installation of the downstream control line.
The Type VSX4 shut-off disk is normally in the open
(reset) position, see Figure 6. If the downstream
pressure below the slam-shut diaphragm increases (or
decreases) until it reaches the slam-shut setpoint, this
diaphragm moves upward (or downward) to release
the trip mechanism which allows the spring force on
the stem to push the disk against the seat, shutting off
all gas ow. To reset the slam shut after gas has been
shut off, refer to the Type VSX4 Instruction Manual for
additional details.
CSB400 SERIES
REGULATOR
REGULATOR VENT
POINTED DOWNWARD
PROTECT VENT PIPE
WITH RAIN CAP
NPS 2 TYPE 289H
RELIEF VALVE
GE27692