Bulletin 71.2:EZH and EZHSO
9
Figure 5. Working Monitoring System Operational Schematic
ATMOSPHERIC PRESSURE
E0876
INLET PRESSURE
LOADING PRESSURE
INTERMEDIATE PRESSURE
PILOT SUPPLY PRESSURE
OUTLET PRESSURE
TYPE PRX:
S - BLEED PORT
B - SUPPLY PORT
L - LOADING PORT
A - SENSING PORT
TYPE SA/2:
V - SENSING PORT
R - PILOT SUPPLY PORT
M - INLET PORT
TYPE EZH
WORKER REGULATOR
TYPE EZH
MONITOR REGULATOR
TYPE PRX-120
TYPE PRX-125
TYPE PRX-120
TYPE SA/2
CHECK
VALVE
CHECK VALVE
TYPE SA/2
V
R
V
R
M
M
S
L
A
B
S
A
B
S
L
A
B
Overpressure Protection
Overpressuring any portion of a regulator or
associated equipment may cause personal injury,
leakage or property damage due to bursting of
pressure-containing parts or explosion of accumulated
gas. Provide appropriate pressure relieving or
pressure limiting devices to ensure that the limits in
the Specications section are not exceeded. Regulator
operation within ratings does not prevent the possibility
of damage from external sources or from debris in the
pipeline. Common methods of external overpressure
protection include relief valves, monitoring regulators,
shutoff devices and series regulation.
Types EZHOSX (Figure 6) and EZHSO-OSX
regulators rely on the integrated slam-shut device
for overpressure (OPSO) or overpressure and
underpressure (OPSO/UPSO) protection. In the event
that outlet pressure rises above or falls below the
pressure setting, slam shut will completely shut off the
ow of gas to the downstream system.
Installation
The EZH and EZHSO Series may be installed in any
position, but it is normally installed in a horizontal
pipeline with the pilot or pilots above the body. The
optimal location for the sense and bleed lines is
between the regulator and the downstream block
valve. If the sense and bleed lines cannot be located
between the EZH and EZHSO Series and downstream
block valve, contact your local Sales Ofce for startup
assistance. See Figures 2 and 3 for typical
piping installations.
Note
To prevent damage to the pilot during
startup, the sense and bleed lines should
be located on the same side of the
downstream block valve.