Emerson EZH and EZHSO Series Pressure Reducing Regulators Arkusz Danych Strona 9

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 28
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 8
Bulletin 71.2:EZH and EZHSO
9
Figure 5. Working Monitoring System Operational Schematic
ATMOSPHERIC PRESSURE
E0876
INLET PRESSURE
LOADING PRESSURE
INTERMEDIATE PRESSURE
PILOT SUPPLY PRESSURE
OUTLET PRESSURE
TYPE PRX:
S - BLEED PORT
B - SUPPLY PORT
L - LOADING PORT
A - SENSING PORT
TYPE SA/2:
V - SENSING PORT
R - PILOT SUPPLY PORT
M - INLET PORT
TYPE EZH
WORKER REGULATOR
TYPE EZH
MONITOR REGULATOR
TYPE PRX-120
TYPE PRX-125
TYPE PRX-120
TYPE SA/2
CHECK
VALVE
CHECK VALVE
TYPE SA/2
V
R
V
R
M
M
S
L
A
B
S
A
B
S
L
A
B
Overpressure Protection
Overpressuring any portion of a regulator or 
associated equipment may cause personal injury, 
leakage or property damage due to bursting of 
pressure-containing parts or explosion of accumulated 
gas. Provide appropriate pressure relieving or 
pressure limiting devices to ensure that the limits in 
the Specications section are not exceeded. Regulator 
operation within ratings does not prevent the possibility 
of damage from external sources or from debris in the 
pipeline. Common methods of external overpressure 
protection include relief valves, monitoring regulators, 
shutoff devices and series regulation.
Types EZHOSX (Figure 6) and EZHSO-OSX 
regulators rely on the integrated slam-shut device 
for overpressure (OPSO) or overpressure and 
underpressure (OPSO/UPSO) protection. In the event 
that outlet pressure rises above or falls below the 
pressure setting, slam shut will completely shut off the 
ow of gas to the downstream system. 
Installation
The EZH and EZHSO Series may be installed in any 
position, but it is normally installed in a horizontal 
pipeline with the pilot or pilots above the body. The 
optimal location for the sense and bleed lines is 
between the regulator and the downstream block 
valve. If the sense and bleed lines cannot be located 
between the EZH and EZHSO Series and downstream 
block valve, contact your local Sales Ofce for startup 
assistance. See Figures 2 and 3 for typical 
piping installations.
Note
To prevent damage to the pilot during
startup, the sense and bleed lines should
be located on the same side of the
downstream block valve.