Power
Indicator
(Green) Off
Make sure there is input voltage.
Internal input fuse open.
Protection
Indicator
(Yellow) On
AC input voltage outside the
normal range.
Correct the AC input voltage to
within the acceptable range.
Moderate load sharing imbalance.
Rectifier not inserted into the slot
completely.
Remove and properly insert the
Rectifier.
Rectifier over-temperature protection, which could be caused by:
1. Remove any object that may
be blocking the fan.
2. Ventilation blocked (inlet or
outlet).
2. Remove any object that may
be blocking the inlet or outlet.
3. Ambient temperature too high
or Rectifier inlet too close to a
heat source.
3. Lower the ambient temperature
or relocate the heat source.
Protection
Indicator
(Yellow)
Flashing
Rectifier communication failure.
Check the communication cables.
Remove and properly insert the
Rectifier.
Output over-voltage shutdown.
Severe load sharing imbalance.
Internal output fuse open.
Remove the Rectifier, wait 30
seconds or more (until the LEDs
on the rectifier extinguish), then
re-insert the Rectifier. If Rectifier
fails to start or shuts down again;
replace the Rectifier.
Alarm
Indicator
(Red)
Flashing
Fan not operating
(Rectifier shuts down).
Table 3
Rectifier Troubleshooting