Emerson NetSure 802 DC Power System Podręcznik Użytkownika Strona 163

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 162
User Instructions Section 5877
Spec. No. 582140000 (Models 802NLDB, 802NLEB and 802NL-B) Issue AQ, January 15, 2013
Chapter 6. System Troubleshooting and Repair Page 6-5
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Rectifier Current Sharing Unbalance
When multiple rectifiers are operating in parallel and the current sharing unbalance
among them is greater than 3%, check if the communications cables are correctly
connected.
If the current sharing unbalance still persists, following the verification suggested above,
then replace the rectifier which has had its current sharing function disabled.
Przeglądanie stron 162
1 2 ... 158 159 160 161 162 163 164 165 166 167 168 ... 187 188

Komentarze do niniejszej Instrukcji

Brak uwag