Types S204 and S206
D400011X012
Instruction Manual
Form 1749
January 2010
www.sherregulators.com
Types S204 and S206 Gas Regulators
!
WARNING
Fisher
®
regulators must be installed,
operated, and maintained in accordance
with federal, state, and local codes, rules
and regulations, and Emerson Process
Management Regulator Technologies,
Inc., instructions.
If the regulator vents gas or a leak
develops in the system, service to the unit
may be required. Failure to correct trouble
could result in a hazardous condition.
Call a gas service person to service
the unit. Only a qualied person must
install or service the regulator.
Introduction
Scope of the Manual
This instruction manual provides instructions and a parts
list for Types S204 and S206 gas service regulators.
Description
Types S204 and S206 gas service regulators are
typically installed on industrial and commercial
applications. Both regulators have a low outlet
pressure shutoff mechanism that shuts gas ow off
if the required minimum outlet pressure cannot be
maintained. Type S206 also has an internal relief valve
that gives partial downstream overpressure protection.
Specications
The Specications table lists the specications for
Types S204 and S206 constructions. The following
information is stamped on the regulator at the factory:
type number, date of manufacture, spring range, port
size, maximum inlet pressure, maximum operating
outlet pressure, and outlet pressure which may
damage regulator parts.
Installation
!
WARNING
Personal injury or system damage
may result if this regulator is installed,
without appropriate overpressure
protection, where service conditions
could exceed the limits given on
the regulator nameplate. Regulator
installations should be adequately
protected from physical damage.
All vents should be kept open to permit
free ow of gas to the atmosphere.
Protect openings against entrance of
rain, snow, insects, or any other foreign
material that may plug the vent or vent
line. On outdoor installations, point the
spring case vent downward to allow
condensate to drain (see Figure 2). This
minimizes the possibility of freezing
and of water or other foreign materials
entering the vent and interfering with
proper operation.
Figure 1. Typical Type S204 Gas Regulator
Przeglądanie stron 0
1 2 3 4 5 6 7 8

Podsumowanie treści

Strona 1 - Types S204 and S206

Types S204 and S206D400011X012Instruction ManualForm 1749January 2010www.sherregulators.comTypes S204 and S206 Gas Regulators!WARNINGFisher® regulato

Strona 2

Types S204 and S2062!WARNINGUnder enclosed conditions or indoors, escaping gas may accumulate and be an explosion hazard. In these cases, the vent sh

Strona 3

Types S204 and S2063Table 1.  Inlet PressureTable 2.  Maximum Outlet Pressure SettingSEAT RING SIZE, INCHES (mm)INLET PRESSURE SETTING, PSIG (bar)Opti

Strona 4

Types S204 and S2064NoteFollow the same procedure if the regulator shuts off during service. A lever (Part No. ORO6172509A, Figure 3) is needed to re

Strona 5

Types S204 and S2065the seat ring. This allows the spring in the back disk assembly to seat the back disk against the seat ring and shut off ow. Th

Strona 6

Types S204 and S2066Figure 6. Type S206 Regulator AssemblyFigure 5.  Type S204 Regulator AssemblyAAVENT6261585560565759184245263321158101471321169282