Emerson 644 Dokumentacja Strona 24

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 23
14
Reference Manual
00809-0200-4728, Rev RA
Section 2: Configuration
April 2015
Configuration
2.5.2 Verify and review configuration with AMS Device Manager
1. Right click on the device and select Configuration Properties from the menu.
2. Navigate the tabs to review the transmitter configuration data.
2.5.3 Verify and review configuration with LOI
Press any configuration button to activate the LOI. Select VIEW CONFIG to review the below
parameters. Use the configuration buttons to navigate through the menu. The parameters to be
reviewed prior to installation include:
Tag
Sensor Configuration
Units
Alarm and Saturation Levels
Primary Variable
Range Values
Damping
2.5.4 Checking transmitter output
Before performing other transmitter on-line operations, review the 644 digital output
parameters to ensure that the transmitter is operating properly and is configured to the
appropriate process variables.
Table 2-3. 644 Device Dashboard Fast Key Sequences
Function
Fast Key sequence
HART 5 HART 7
Alarm Values 2, 2, 5, 6 2, 2, 5, 6
Damping Values 2, 2, 1, 5 2, 2, 1, 6
Lower Range Value (LRV) 2, 2, 5, 5, 3 2, 2, 5, 5, 3
Upper Range Value (URV) 2, 2, 5, 5, 2 2, 2, 5, 5, 2
Primary Variable 2, 2, 5, 5, 1 2, 2, 5, 5, 1
Sensor 1 Configuration 2, 1, 1 2, 1, 1
Sensor 2 Configuration
(1)
(1) Available only if option code (S) or (D) is ordered.
2, 1, 1 2, 1, 1
Ta g 2, 2, 7, 1, 1 2, 2, 7, 1, 1
Units 2, 2, 1, 5 2, 2, 1, 4
Przeglądanie stron 23
1 2 ... 19 20 21 22 23 24 25 26 27 28 29 ... 181 182

Komentarze do niniejszej Instrukcji

Brak uwag