Electrical Installation
4.3 Wiring and powering the transmitter
All power to the transmitter is supplied over the signal wiring. Use ordinary copper wire of
sufficient size to ensure the voltage across the transmitter power terminals does not drop below
12.0 Vdc.
If the sensor is installed in a high-voltage environment and a fault condition or installation error
occurs, the sensor leads and transmitter terminals could carry lethal voltages. Use extreme
caution when making contact with the leads and terminals.
Note
Do not apply high voltage (e.g., ac line voltage) to the transmitter terminals. Abnormally high
voltage can damage the unit. (Sensor and transmitter power terminals are rated to 42.4 Vdc. A
constant 42.4 volts across the sensor terminals may damage the unit.)
For multichannel HART installations, see above. The transmitters will accept inputs from a
variety of RTD and thermocouple types. Refer to Figure 2-6 on page 19 when making sensor
connections.
The sensor wiring diagram is located on the device’s top label below the terminal screws. See
Figure 4-1 and Figure 4-2 for where to find and how to correctly wire all sensor types to the 644
transmitter.