Emerson DLC3010 Przewodnik Szybki Start Strona 33

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 44
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 32
Quick Start Guide
D103214X012
DLC3010 Digital Level Controller
September 2014
33
Figure 15. FM Loop Schematic
28B5745‐C
1. THE INSTALLATION MUST BE IN ACCORDANCE WITH
 THE NATIONAL ELECTRIC CODE (NEC), NFPA 70, ARTICLE
 504 AND ANSI/ISA RP12.6.
2. CLASS 1, DIV 2 APPLICATIONS MUST BE INSTALLED AS SPECIFIED
 IN NEC ARTICLE 501-4(B). EQUIPMENT AND FIELD WIRING IS
 NON-INCENDIVE WHEN CONNECTED TO APPROVED BARRIERS WITH
 ENTITY PARAMETERS.
3. LOOPS MUST BE CONNECTED ACCORDING TO THE BARRIER
 MANUFACTURERS INSTRUCTIONS.
4. MAXIMUM SAFE AREA VOLTAGE SHOULD NOT EXCEED 250 Vrms.
5. RESISTANCE BETWEEN BARRIER GROUND AND EARTH GROUND
 MUST BE LESS THAN ONE OHM.
6. NORMAL OPERATING CONDITIONS 30 VDC 20 mADC.
7. IF HAND-HELD COMMUNICATOR OR MULTIPLEXER IS USED,
 IT MUST BE FM APPROVED AND INSTALLED PER THE
 MANUFACTURE'S CONTROL DRAWING.
8. FOR ENTITY INSTALLATION (I.S. AND N.I.);
Vmax > Voc, or Vt Ci + Ccable < Ca
Imax > Isc, or It Li + Lcable < La
Pi > Po, or Pt
9. THE APPARATUS ENCLOSURE CONTAINS ALUMINUM AND IS
 CONSIDERED TO CONSTITUTE A POTENTIAL RISK OF IGNITION
 BY IMPACT OR FRICTION. AVOID IMPACT AND FRICTION DURING
 INSTALLATION AND USE TO PREVENT RISK OF IGNITION.
HAZARDOUS LOCATION
I.S. CLASS I,II,III DIV 1, GROUPS A,B,C,D,E,F,G
N.I. CLASS I, DIV 2, GROUPS A,B,C,D
NON-HAZARDOUS LOCATION
FM APPROVED BARRIER
SEE NOTE 7
FISHER TYPE DLC3010
Vmax = 30 VDC
Imax = 226 mA
Ci - 5.5 nF
Li = 0.4 mH
Pi = 1.4 W
Przeglądanie stron 32
1 2 ... 28 29 30 31 32 33 34 35 36 37 38 ... 43 44

Komentarze do niniejszej Instrukcji

Brak uwag