CONFIGURE
! Using a terminal emulation software package, like HyperTerminal™,
open a direct connection to the card.
BAUD RATE: 9600
DATA BITS: 8
PARITY: None
STOP BITS: 1
FLOW CONTROL: None
! Press “ENTER” for the Main Menu.
! Select option “2” and follow the instructions to enter an IP
ADDRESS, NETMASK, and GATEWAY.
! Return to the Main Menu and select option “x” to exit and save
CONFIGURE
! Using a terminal emulation software package, like HyperTerminal™,
open a direct connection to the card.
BAUD RATE: 9600
DATA BITS: 8
PARITY: None
STOP BITS: 1
FLOW CONTROL: None
! Press “ENTER” for the Main Menu.
! Select option “2” and follow the instructions to enter an IP
ADDRESS, NETMASK, and GATEWAY.
! Return to the Main Menu and select option “x” to exit and save
INSTALL
CONNECT CABLE
· Locate the Intellislot bay on the back of your
Liebert PowerSure Interactive, UPStation GXT, or
Nfinity UPS (Use the Intellislot labeled COM1).
· Remove the plastic Intellislot cover.
· Insert the OpenComms Web Card into the
Intellislot bay.
· Secure the card with the previously removed
screws.
· Connect Ethernet cable.
· Locate the blue serial configuration cable (null
modem) that shipped with the card.
· Connect one end of the configuration cable to the
DB-9 port on the card.
· Connect the other end of the configuration cable
to a COM port on your PC.
DHCP: The card ships with DHCP service enabled. The MAC
address is printed on a sticker affixed to the top of the card.
OR
Static IP: To assign a static IP address, you will need to use the
to configure the card. Proceed to steps 2 & 3.