Emerson Liebert FPC Instrukcja Użytkownika

Przeglądaj online lub pobierz Instrukcja Użytkownika dla Networking Emerson Liebert FPC. Liebert NX 480V – Ancillary BDC Instrukcja obsługi

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 58
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 0
Aplicación de rango medio para famila de UPS
Emerson Network Power
Enabling Business-Critical Continuity™
Przeglądanie stron 0
1 2 3 4 5 6 ... 57 58

Podsumowanie treści

Strona 1 - Emerson Network Power

Aplicación de rango medio para famila de UPS Emerson Network Power Enabling Business-Critical Continuity™

Strona 2 - NX Family Product Line

Liebert NX 480V- Paralleling Options  Protect your investment by adding only the capacity you need – Change your growth increment when your business

Strona 3 - Discharge

Liebert NX 480V - Greater Efficiency 75.0%80.0%85.0%90.0%95.0%100.0%10%15%20%25%30%35%40%45%50%55%60%65%70%75%80%85%90%95%100%Percent LoadEfficiencyNp

Strona 4 - Liebert NX limits THD

Liebert NX 480V – Ancillary BDC BDC – Bypass Distribution Cabinet BDC Tie breaker UPS CB1 CB3 CB3A 4 W + G UPS Output 208V 220V 3 W + G UPS Input 480V

Strona 5 -  Bypass

Liebert NX 480V – Ancillary BDC BDC – Bypass Distribution Cabinet with Input and Output Transformer Tie breaker UPS CB1 CB3 CB3A 4 W + G UPS Output 20

Strona 6 - Single Corded

Liebert NX 480V - Key Benefits  Softscaletm technology enables simpler, faster response to changes in data center power requirements  Softscaletm al

Strona 7 - Paralleling Enclosures

15 Liebert NXL 480V/480V, 575/575V , 600/600V, 0.9 output pf 250kVA/225kW 300kVA/270kW 400kVA/360kW 500kVA/450kW 625kVA/562kW 750kVA/675kW

Strona 8

What’s New in NXL  Employs latest generation IGBTs and advanced inverter logic with active harmonic control  Optimized energy efficiency with better

Strona 9 - Liebert NX 480V - Softscale

Liebert NXL UPS Enterprise-Scale UPS Protection for Medium/Large Data Centers  Advanced Global UPS Platform  Robust design allows operation at 100%

Strona 10 -  Paralleling Cabinet

18 NXL, Single Module System One-Line 6-pulse rectifier MIBOutputMBB3PCB2BFBEBIBEGFBOACFBOACGECMBJN NEGTo BatteriesATrap DisconnectNon isolated other

Strona 11 - Typical Loading 40-70%

19 Liebert NXL – 300 kVA First UPS to UL 1778 Rev 4 Color HMI Screen Removable air filters Optional EMO Button Customer Interface Board

Strona 12 - Tie breaker

NX Family Product Line 10, 15, 20, 30, 40, 60 80, 100 ,120, 140, 160, 200 kVA 14,000 installed Worldwide

Strona 13

20 Liebert NXL – 300 kVA IGBT Inverters Rectifier Static Switch Power Supplies Input Filter Inductors Input Series Inductors DC Choke Input Filter

Strona 14 -  Softscale

21 Battery Cabinet Conduit Landing Up to 400kVA No Tie Cabinet Required Strap Plates For Cabinet to Cabinet Short bus on stand alone cabinet Top Acces

Strona 15 - Liebert NXL

Maintenance Bypass Cabinet Configurations  Two Breaker MBC – 1,2 or 3 inputs – Single input bus jumper in module – Bypass input off MBP Maint. Bypass

Strona 16 - What’s New in NXL

23 Liebert NXL – Battery Cabinets  Battery cabinet(s) may be right or left side installed – Connected with drop-in Buss links  EXCEPT when applied w

Strona 17 - Liebert NXL UPS

0.6 0.65 0.7 0.75 0.8 0.85 0.9 0.95 1 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 % eff (+/-0.5%) % Load Liebert NXL 400kVA AC-AC Efficiencies (

Strona 18 - 6-pulse rectifier

Liebert NXL, Single Module System One-Line, 12-pulse rectifier MIBOutputMBB3PCB2BFBEBIBEGFBOACFBOACGECMBJN NEGATrap DisconnectCB112P isolated12P non

Strona 19 - Liebert NXL – 300 kVA

26 Liebert NXL – One-Line 1+N (Distributed Static Switch) Bypass Sharing Inductor

Strona 20

27 Liebert NXL – One-Line N+1 (System Static Switch) System rated Static Switch

Strona 21 - Battery Cabinet

28 HMI Display Multi-purpose display

Strona 22 - Static Bypass

29 Battery Discharge Graph

Strona 23

Wider rectifier operating range means less battery use and lower cost of ownership 480 528 384 Rectifier ON -20% at full load 480 384 Rectifier ON 480

Strona 24 - 92.5%-94.5%

30 Battery Cycle Monitor

Strona 25

31 On Maintenance Bypass

Strona 26 - Liebert NXL – One-Line

Large UPS – Comparisons Characteristic PW 9395 Liebert Series 610 Liebert NXL Redundant Power Supply Yes (2) Yes (2) Yes (4) Overload Capacity L

Strona 27 - Static Switch

Benefits of a Transformer Based UPS  Personnel Safety  Helps mitigate arc flash – Full galvanic isolation – DC ground fault  Availability – Dual in

Strona 28 - HMI Display

Data Center Applications – 3PH UPS BATTERIES UPS: Uninterruptible Power System

Strona 29 - Battery Discharge Graph

TIER 4: No Downtime Distributed Redundant Dual Input PDU LBS UPS 1 Load STS Load STS Load Dual Input Load Utility Source / Generator #2 Utility Sourc

Strona 30 - Battery Cycle Monitor

Foundation Power Center (FPC)  So what is a Foundation Power Center?  It is a PPC in a Foundation  We have repackaged the PPC to make it fit in wit

Strona 32

Liebert FPC Specifications  Ratings – 15, 30, 50, 75, 100, 125, 150, 200, 225, 300kVA  Voltages – Input – 208, 380, 400, 415, 480, 600V – Output – 2

Strona 33 -  Flexibility

Liebert FPC Front View Main Input Breaker Subfeed Breakers PMP NIC Transformer

Strona 34 - BATTERIES

 Input THD of less than 5% and near unity PF 100% linear 100% nonlinearTHDi_A (%) 2.269 4.328THDi_B (% ) 1.972 4.082THDi_C (% ) 1.882 4.244PF_A 0.9

Strona 35 - Types of Systems

Liebert FPC Rear View

Strona 36 - It is a PPC in a Foundation

Liebert FPC Rear View Pnlbd Main Breaker

Strona 37 - Liebert FPC

Liebert FPC Specifications  Standard Unit includes – Main input breaker with shunt trip – Copper Isolation transformer – Computer Grade Grounding – F

Strona 38 -  Frequency

Data Center Applications – Distribution PDU PDU RDC or FDC RDC or FDC CRITICAL IT LOADS 480 VAC 208 VAC 208 VAC Foundation Distribution Center • Lo

Strona 39 - Liebert FPC Front View

Data Center Applications – RDC (or FDC) RDC RDC RDC

Strona 40 - Liebert FPC Rear View

Typical System Applications Figure 1 at left shows the two most-common uses of the RDC, in themiddle or at the end of a section ofequipment racks. Fig

Strona 41

Foundation Distribution Center (FDC)  So what is a Foundation Distribution Center?  It is a RDC in a Foundation  We have repackaged the RDC to make

Strona 42 -  Standard Unit includes

Liebert FDC Specifications  Sizes – Same as a 19” rack – 23.5”Wx38”Dx77”H  Input/Output Voltages - 208/120V  One, two, four inputs  4 panelboar

Strona 44

Liebert FDC Specifications  Enclosure – 23.5”Wx38”Dx77”H – Color – Black – Doors – removable front and back (same doors as offered with Foundation)

Strona 45 - Figure 3

Advantage - High Overload Capacity  Inverter mode – 100 – 110%, 1hour – 110 – 125%, 10min – 125 – 150%, 1min  Bypass – 100 – 135% Long term – 135 –

Strona 46 - It is a RDC in a Foundation

Main Panelboard Breakers  Main Panelboard Breakers – Located remote from panelboards  Square D Q2 is standard – 225A, 10 kAIC at 208 Vac – regardl

Strona 47 -  Bottom exit

Opportunities begin with The Rack: DCM 52

Strona 48 - Liebert FDC

Add Row Based Power: NX 53

Strona 49 -  Enclosure

Add Liebert MB Modular Busway…. 54

Strona 50 -  Main Panelboard Breakers

Add Liebert MPH/X Rack PDUs… 55

Strona 51

Add Liebert CRV Row Based Cooling…. 56

Strona 52 - Add Row Based Power: NX

Add SmartAisle Containment… 57

Strona 53

 Busway Power Distribution  Liebert XDV Mounting  SmartAisle Integration begin with Our Rack DCM Top Cover 58

Strona 55 - Add Liebert CRV Row Based

Liebert NX - Load Bus Sync (LBS) Option  Provides necessary communications to allow two “independent” UPS systems to synchronize for downstream equip

Strona 56 - Add SmartAisle Containment…

Liebert NX 1+1 Parallel Redundant – Dual Bus System Dual Corded Equipment Single Corded Equipment STS Parallel Cables Parallel Cables Paralleling Enc

Strona 57 -  SmartAisle

Liebert NX 480V - Product Introduction  The Liebert NX 480V / 40 – 200 kVA • Main key attributes • 480V standard voltage, 0.9 power factor • Minimal

Strona 58 - Thanks!

Liebert NX 480V - Softscale Critical load FPC 40 kVA 60 kVA 80 kVA Softscale Upgrade • Select the capacity you need • Buy the 20kVA upgrade and buy it

Komentarze do niniejszej Instrukcji

Brak uwag