Supported Modbus Points
35
Table 24 Liebert DS
- Status and Coil
Data Description Status Coil
Number
of Bits Notes
Clogged Filters 10076 - 1
-
Supply Sensor Failure 10077 - 1
-
Freecool Temp Sensor 10078 - 1
-
Sensor A Failure 10079 - 1 -
Unit Hrs Exceeded 10080 - 1 -
Comp 1 Hrs Exceeded 10081 - 1 -
Comp 2 Hrs Exceeded 10082 - 1 -
FC Hrs Exceeded 10083 - 1 -
El Heat1 Hrs Exceeded 10084 - 1 -
El Heat2 Hrs Exceeded 10085 - 1 -
El Heat3 Hrs Exceeded 10086 - 1 -
HW/HG Hrs Exceeded 10087 - 1 -
Hum Hrs Exceeded 10088 - 1 -
Dehum Hrs Exceeded 10089 - 1 -
Network Failure 10091 - 1 -
No Connection W/Unit 10092 - 1 -
Unit(s) Disconnected 10093 - 1 -
Unit Code Missing 10094 - - -
Unit Code Mismatch 10095 - - -
Call Service 10096 - - -
Low Memory 1 10097 - - -
RAM / Battery Failure 10098 - - -
HCB not connected 10099 - - -
(Parallel Flash) Memory 1 Fail 10100 - - -
(Serial Flash) Memory 2 Fail 10101 - - -
Customer Input 1 10104 - - -
Customer Input 2 10105 - - -
Customer Input 3 10106 - - -
Customer Input 4 10107 - - -
Digital Scroll Compressor 1 Sensor Fail 10108 - - -
Digital Scroll Compressor 2 Sensor Fail 10109 - - -
Reference Document: ST100I&C PA Parameters and Events, Version 18.0
1. Any non-recognized alarm code by current firmware received from the DS control will trigger this event.