Emerson OpenComms-485 Instrukcja Użytkownika Strona 44

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 52
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 43
Supported Modbus Points
40
Table 26 Liebert XDF
- Status and Coil
Data Description Status Coil Number of Bits Notes
Sensor A Failure
10079 - 1
-
Unit Hrs Exceeded
10080 - 1
-
Comp 1 Hrs Exceeded
10081 - 1
-
Comp 2 Hrs Exceeded
10082 - 1
-
FC Hrs Exceeded
10083 - 1
-
El Heat1 Hrs Exceeded
10084 - 1
-
El Heat2 Hrs Exceeded
10085 - 1
-
El Heat3 Hrs Exceeded
10086 - 1
-
HW/HG Hrs Exceeded
10087 - 1
-
Hum Hrs Exceeded
10088 - 1
-
Dehum Hrs Exceeded
10089 - 1
-
Network Failure
10091 - 1
-
No Connection W/Unit 1
10092 - 1
-
Unit(s) Disconnected
10093 - 1
-
Unit Code Missing
10094 -
- -
Unit Code Mismatch
10095 -
- -
Call Service
10096 -
- -
Low Memory 1
10097 -
- -
Ram / Battery Failure
10098 -
- -
HCB Not Connected
10099 -
- -
(Parallel Flash) MEMORY 1 FAIL
10100 -
- -
(Serial Flash) MEMORY 2 FAIL
10101 -
- -
Customer Input 1
10104 -
- -
Customer Input 2
10105 -
- -
Customer Input 3
10106 -
- -
Customer Input 4
10107 -
- -
Digital Scroll Compressor 1
Sensor Fail
10108 -
- -
Digital Scroll Compressor 2
Sensor Fail
10109 -
- -
Low Int Temperature
10110 -
- -
High Ext Dewpoint
10111 -
- -
Cabinet Temp Sensor Fail
10112 -
- -
Cabinet Humidity Sensor Fail
10113 -
- -
Ambient Temp Sensor Fail
10114 -
- -
Unit Disabled
10129 -
- -
Unit Shut Down
10130 -
- -
Unit Synchronization
10131 -
- -
Comp 1 Short Cycle
10132 -
- -
Comp 2 Short Cycle
10133 -
- -
Przeglądanie stron 43
1 2 ... 39 40 41 42 43 44 45 46 47 48 49 50 51 52

Komentarze do niniejszej Instrukcji

Brak uwag