Type EZL
6
Type EZL Working Monitor
E0946
January 2008
Type EZL
INLET PRESSURE
OUTLET PRESSURE
ATMOSPHERIC PRESSURE
LOADING PRESSURE
INTERMEDIATE PRESSURE
Installation
WARNING
!
Personal injury or equipment damage,
due to bursting of pressure-containing
parts may result if this regulator is
overpressured or is installed where
service conditions could exceed the limits
on the appropriate nameplate or where
conditions exceed any rating of the
adjacent piping or piping connections.
To avoid such injury or damage, provide
pressure-relieving or pressure-limiting
devices to prevent service conditions
from exceeding those limits. Also, be sure
the installation is in compliance with all
applicable codes and regulations.
Additionally, physical damage to the
regulator could break the pilot off the
main valve, causing personal injury and
property damage due to bursting of
pressure-containing parts. To avoid such
injury and damage, install the regulator in
a safe location.
All Installations
A Type EZL regulator bleeds no gas to atmosphere
during normal operation, thus making the regulator
suitable for installation in pits and other enclosed
locations without elaborate venting systems. This
regulator also can be installed in pits subject to ooding
by venting the pilot spring case above the expected
ood level so that the pilot setting can be referenced to
atmospheric pressure.
1. Only personnel qualied through training and
experience should install, operate and maintain a
regulator. Before installation, make sure that there
is no damage to or debris in the regulator. Also,
make sure that all tubing and piping are clean
and unobstructed.
Figure 5. Working Monitoring System Operational Schematic
E0946
TYPE EZL MAIN VALVE TYPE EZL MAIN VALVE
P590 SERIES PILOT
SUPPLY FILTER
TYPE 6352 PILOT
TYPE 6352 PILOT
TYPE 161EBM
MONITOR PILOT
P590 SERIES
PILOT SUPPLY
FILTER
INLET PRESSURE
OUTLET PRESSURE
LOADING PRESSURE
INTERMEDIATE PRESSURE
ATMOSPHERIC PRESSURE
Komentarze do niniejszej Instrukcji