Type EZL
7
Note
When upgrading Fisher
®
control valves,
such as Types ET, ED and ES make sure

2. Install the regulator so that the ow arrow on the
main valve matches the ow direction of process
uid through the regulator.
3. Apply pipe comlb to the external pipeline threads
before installing a regulator with threaded end
connections. Use gaskets between pipeline and
regulator anges when installing a regulator with
anged end connections. When installing buttweld
end connections, remove trim before welding and
make sure to use approved welding practices.
Use approved piping procedures when installing
the regulator.
WARNING
!
A regulator may vent some gas to the

gas service, vented gas may accumulate,
causing personal injury, death or
property damage due to bursting of
pressure-retaining parts. Vent a regulator
in hazardous gas service to a remote,
safe location away from air intakes or
any hazardous location. The vent line or
stack opening must be protected against
condensation or clogging.
4. Pilots have a 1/4 in. NPT vent connection in the
spring case. To remotely vent gas from the spring
case, remove the screened vent and connect
1/4 in. / 6.4 mm piping or tubing to the spring case
connection. The piping or tubing should vent to
a safe location, have as few elbows as possible
and have a screened vent on its exhaust. Install
the regulator and any remote vent piping or tubing
so that the vent is protected from condensation,
freezing or substances that may clog it.
CAUTION
To avoid freezeup because of pressure
drop and moisture in the gas, use anti-
freeze practices, such as heating the
supply gas or adding a de-icing agent to
the supply gas.
5. Run a 3/8 in. / 9.5 mm outer diameter or larger pilot
supply line from the upstream pipeline to the lter
inlet as shown in Figure 3, bushing the line down
to t the 1/4 in. threaded NPT lter connection.
Do not make the upstream pipeline connection in
a turbulent area, such as near a nipple, swage or
elbow. If the maximum pilot inlet pressure could
exceed the pilot rating, install a separate reducing
regulator in the pilot supply line. Install a hand valve
in the pilot supply line and provide vent valves
to properly isolate and relieve the pressure from
the regulator.
6. Attach a 1/2 in. / 12 mm piping or tubing
downstream control line to the 1/2 in. threaded NPT
control line connection on the actuator casings.
Connect the other end of the control line to the
pipeline downstream of the regulator. Do not attach
the control line near any elbow, swage, block valve
or any other location that might cause turbulence.
Install a full port ball valve in the control line to
shutoff the control pressure when using the bypass.
7. If a quick acting solenoid is to be installed
downstream of a regulator, the regulator and
solenoid should be located as far apart as practical.
This will maximize the gas piping volume between
the regulator and solenoid and improve the
regulator response to quick changing ow rates.
8. Consult the appropriate instruction manual for
installation of an optional pneumatic or electric
remote control drive unit. For optional remote
pneumatic loading of a 6350 or 61 Series pilot,
make the loading piping connections to the
1/4 in. NPT vent connection.
Wide-Open Monitor Regulator (Figure 4)
1. Follow the procedures in the All Installations
section and then continue with step 2 of
this section.
2. Connect the control line of the wide-open
monitoring regulator to the downstream piping
near the working regulator control line connection.
During normal operation, the wide-open regulator
stands wide-open with the pressure reduction
being taken across the working regulator. Only
in case of working regulator failure does the
wide-open monitoring regulator take control at its
slightly higher setting.
Regardless of which regulator is used as the monitor,
it should be equipped with a pilot supply regulator
set to limit the pilot supply pressure to 10 to 15 psig /
0.69 to 1.0 bar above control pressure. Since the