NetSure
™
ACU+ Controller (Advanced Control Unit Plus)
User Instructions, UM1M820BNA (Issue AK, March 3, 2014)
Spec. No: 1M820BNA, 1M820DNA Code: UM1M820BNA
Model No: M820B, M820D Issue AK, March 3, 2014
•
If load fluctuation is less than this value,
rectifiers are not turned on or off for Energy
Optimization.
•
Energy Optimization is disabled if
the load is greater than this setting.
•
This is the time period that rectifiers
are turned on and off to maintain an equal operating
time for all rectifiers in the system.
•
Time all rectifiers are turned on at
End of Cycle.
•
When the Energy Optimization
feature determines a rectifier can be switched off,
this is the time delay before the rectifier is switched
off.
•
Sets the Input Current Limit point for all
rectifiers.
•
Allows the system to use rectifiers of
different output capacity. When set to derated power,
the output capacity of the higher capacity rectifiers are
set to the capacity of the lowest.
•
Enables or disables the Diesel Power Limit
feature. This feature limits rectifier output power to a
percentage of maximum when AC input is supplied by a
diesel-alternator set.
•
Designates which digital input
controls operation of the Diesel Power Limit feature.
•
Sets, as a percentage, the maximum
output power at which rectifiers can operate when:
1. the Diesel Power Limit feature is enabled and 2. a
digital input signal is received from the connected
diesel-alternator set.
•
Enables or disables adjusting the output
current limit point.
By default this is set to disabled. When disabled,
rectifier current limit is set in the rectifier (not via
the ACU+) at the maximum current limit point.
•
Allows a User to set the output current
limit point when the “Current Limit” setting above is set
to enabled.
RECT #1 MENU
Main Menu / Settings / Rectifier / Rect #1
Note: For WEB Interface; menu items are found under Device
Information / Rectifier Group / Rectifier #1 / Settings Tab.
Rect #1" Parameter Settings:
•
Sets the rectifier position in the system.
•
Indicates the phase connected to the rectifier
input.
Battery
BASIC MENU
Main Menu / Settings / Battery / Basic
Note: For WEB Interface; menu items are found under Device
Information / Battery Group / Settings Tab.
"Basic" Parameter Settings:
•
Sets the number of battery shunts in
the system.
•
Selects whether or not the ACU+
calculates the battery current in the case of no battery
shunt (load shunt required).
•
Battery low capacity alarm set point.
•
Enables or disables battery charge
current limit.
•
Sets the BTRM (Battery Thermal
Runaway Management) temperature sensor. Note that
this temperature sensor MUST be set as a battery
temperature sensor. Select "None", or the temperature
probe (SMTemp8 T8 / ... / SMTemp8 T1 / ... / SMTemp1
T8 / ... / SMTemp1 T1 / EIB T2 / EIB T1 / IB2 T2 / IB2 T1).
You can also select Maximum or Average which takes the
maximum or average reading of the temperature probes
(any of SMTemp8 T8 / ... / SMTemp8 T1 / ... / SMTemp1
T8 / ... / SMTemp1 T1 / EIB T2 / EIB T1 / IB2 T2 / IB2 T1) set
as battery temperature probes. When used with an SM-
BRC, you can select to average the SM-BRC temperature
probe readings.
The BTRM sensor is the sensor which is used for the
High Temperature Disconnect (HTD) Feature.
•
Allows you to set a high BTRM
temperature alarm 2 point. If battery temperature
exceeds the “BTRM Temp High2” setting, system voltage
is lowered to the “BTRM Voltage” setting (if BTRM Action
is enabled).
•
Allows you to set a high BTRM
temperature alarm 1 point.
•
•
Disables the Battery Thermal Runaway
Management feature.
•
Sets the Battery Thermal Runaway
Management feature to reducing the output voltage
when battery temperature exceeds the BTRM Temp
setting.