NetSure
ACU+ Controller (Advanced Control Unit Plus)
User Instructions, UM1M820BNA (Issue AK, March 3, 2014)
Spec. No: 1M820BNA, 1M820DNA Code: UM1M820BNA
Model No: M820B, M820D Issue AK, March 3, 2014
70
Table 5
Full Alarm Name WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description Action to Correct
SM Temp Group (SM-Temp Module must be present in system)
(SM Temp Group)
SM Temp Lost
(SMTemp Lost)
SM-Temp cannot be detected by the
Controller.
Reset the SMTemp Lost alarm.
Replace defective SM-Temp.
SM Temp 1-8 (SM-Temp Module must be present in system)
(SMTemp 1-8)
Communication Interrupt
(Comm Interrupt)
SM-Temp has lost communications
with the Controller.
Check communications cables.
Temperature Probe 1
Shorted
(Probe1 Short)
Probe shorted.
Replace temperature probe.
Temperature Probe 8
Shorted
(Probe8 Short)
Probe shorted.
Temperature Probe 1 Open
(Probe1 Open)
Probe open.
Replace temperature probe.
Temperature Probe 8 Open
(Probe8 Open)
Probe open.