Programming Battery Setup for the BDS
20-10
20.4. Battery Setup: Float Alarms (BDS)
String View > Setup|Battery|Float Alarms
The following appear on the Float Alarms dialog box.
Figure 83. Battery Setup - Float Alarms (BDS)
Float Alarms Enable or Disable - Global control of all float alarms for local alarm status
and alarm contact activation. Select Enable for the call-out of float alarms and digital input
alarms. When Disable is selected, the String Status column on the String Status screen
indicates Alarms Disabled.
Cell Resistance Threshold - Global applies the alarm level in the Cell Resistance
(microhms) field to all cells. Individual and Input Level sets alarm levels on a cell basis
using the Cell Resistance Alarm Levels box.