Emerson BDS-256XL Podręcznik Użytkownika Strona 137

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 205
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 136
Using the Report Generator
22-3
22.2. Detail Cell Resistance Report
String View > View|Reports|Detail|Cell Resistance
To create a Detail Cell Resistance report, click Cell Resistance. The Detail Cell Resistance
Setup box appears.
Figure 97. Detail Cell Resistance Setup
The items on the Detail Cell Resistance Setup box are the same as those on the Detail Cell
Voltage Setup box (refer to Detail Cell Voltage Report), with the following exceptions.
To ignore BMDM thresholds, click Override Preset Thresholds. In the Baseline box, type
the resistance in microhms. In the % Above Baseline box, type the percentage above which a
measurement will be in violation. For example, if the baseline resistance is 300 microhms and
the percentage is 10%, any data above 330 microhms violates threshold.
Select Show Average Trend to generate a graph that shows the average resistance of all the
cells in the string for each date selected.
Przeglądanie stron 136
1 2 ... 132 133 134 135 136 137 138 139 140 141 142 ... 204 205

Komentarze do niniejszej Instrukcji

Brak uwag