Quick Start Guide00825-0200-4728, Rev DBFebruary 2015NoteBefore installing the transmitter, confirm the correct device driver is loaded on the host sy
February 201510Quick Start GuideStep 3: Mount the transmitterMount the transmitter at a high point in the conduit run to prevent moisture from drainin
Quick Start Guide11February 2015Head mount transmitter with threaded sensor installation (2 or 3 conduit entries)1. Attach the thermowell to the pipe
February 201512Quick Start GuideField mount transmitter with threaded sensor installation1. Attach the thermowell to the pipe or process container wal
Quick Start Guide13February 2015Step 4: Wire and apply powerWire the sensor to the transmitterThe wiring diagram is located on the device’s top label
February 201514Quick Start GuideFigure 6. 644 Field Mount - Single and Dual Input Wiring DiagramsPower the transmitterAn external power supply is req
Quick Start Guide15February 2015Load limitationThe power required across the transmitter power terminals is 12 to 42.4 Vdc (the power terminals are ra
February 201516Quick Start GuideOption 21. Connect signal wiring shield to the sensor wiring shield.2. Ensure the two shields are tied together and el
Quick Start Guide17February 2015Grounded thermocouple inputsOption 11. Ground sensor wiring shield at the sensor.2. Ensure the sensor wiring and signa
February 201518Quick Start GuideStep 5: Perform a loop testThe Loop Test command verifies transmitter output, loop integrity, and operation of any rec
Quick Start Guide19February 2015Safety instrumented systemsFor Safety Certified installations, refer to the Rosemount 644 Reference Manual (document n
February 20152Quick Start GuideNOTICEThis guide provides basic guidelines for Rosemount 644 transmitters. It does not provide instructions for configu
February 201520Quick Start GuideProduct CertificationsEuropean Directive InformationA copy of the EC Declaration of Conformity can be found at the end
Quick Start Guide21February 2015Certificate: 3044581 [Headmount HART]Standards: FM Class 3600: 2011, FM Class 3610: 2010, FM Class 3611: 2004,FM Clas
February 201522Quick Start GuideI1 ATEX Intrinsic SafetyCertificate: [Headmount HART]: Baseefa12ATEX0101X[Headmount Fieldbus/PROFIBUS]: Baseefa03ATEX0
Quick Start Guide23February 2015InternationalE7 IECEx FlameproofCertificate: IECEx FMG 12.0022XStandards: IEC 60079-0:2011, IEC 60079-1:2007-04, IEC
February 201524Quick Start GuideNK IECEx DustCertificate: IECEx FMG 12.0022XStandards: IEC 60079-0: 2011, IEC 60079-31: 2008Markings: Ex tb IIIC T1
Quick Start Guide25February 2015ChinaE3 China FlameproofCertificate: GYJ111385Standards: GB3836.1-2000, GB3836.2-2000, GB12476.1-2000Markings: Ex
February 201526Quick Start GuideI3 China Intrinsic SafetyCertificate: GYJ111384XStandards: GB3836.1-2000, GB3836.4-2000Markings: Ex ia IIC T4/T5/
Quick Start Guide27February 2015When Options select Enhanced PerformanceTerminals of power supply (+, -)Terminals of sensor (1,2,3,4)3. This product c
February 201528Quick Start GuideN3 China Type nCertificate: GYJ101421Standards: GB3836.1-2000, GB3836.8-2003Markings: Ex nA nL IIC T5/T6Special Co
Quick Start Guide29February 2015JapanE4 Japan FlameproofCertificate: TC20671 [J2 with LCD], TC20672 [J2], TC20673 [J6 with LCD], TC20674 [J6]Markings:
Quick Start Guide3February 2015System readinessConfirm HART revision capability If using HART based control or asset management systems, please confi
February 201530Quick Start GuideTable 4. Process TemperaturesT6 T5 T4 T3 T2 T1 T130Maximum ambient+40 °C +60 °C +60 °C +60 °C +60 °C +60 °C +70 °CSen
Quick Start Guide31February 2015Figure 8. EC Declaration of Conformity for 644 Temperature Transmitter
February 201532Quick Start Guide
Quick Start Guide33February 2015
February 201534Quick Start Guide
Quick Start Guide35February 2015
Rosemount World HeadquartersEmerson Process Management 6021 Innovation BlvdShakopee, MN 55379, USA+1 800 999 9307 or +1 952 906 8888+1 952 949 7001 RF
February 20154Quick Start GuideTransmitter installationStep 1: Set the alarm switchSet the 644 alarm switch before putting the device into operation.W
Quick Start Guide5February 2015Step 2: Verify configurationVerify the configuration of the Rosemount 644 device upon receiving your transmitter using
February 20156Quick Start GuideFigure 2. Device Dashboard Field Communicator InterfaceTable 2. Device Revision 8 and 9 (HART 5 and 7), DD Revision 1
Quick Start Guide7February 2015Loop Test 3, 5, 1 3, 5, 1Locate DeviceN/A3, 4, 6, 2Lock StatusN/A1, 8, 3, 8LRV (Lower Range Value) 2, 2, 5, 5, 3 2, 2
February 20158Quick Start GuideInput or verify Callendar Van-Dusen constantsIf sensor matching is being used with this combination of a transmitter an
Quick Start Guide9February 2015Figure 4. LOI MenuSwitch HART revision modeNot all systems are capable of communicating with HART Revision 7 protocol.