Type 75A Water Pressure Regulator
Application
The Type 75A is designed to reduce domestic or
industrial water pressures to a constant pressure,
thus protecting plumbing xtures and meters from
high-pressure surges. As shown in Figure 1, it is self-
contained, requiring no external control line
for operation.
Installation
Check the unit for shipment damage. Clean all foreign
material from the pipelines and regulator interior.
Install the Type 75A in a horizontal line with the spring
case above or below the line, and with ow through
the regulator as indicated by the arrow cast on the
body. Coat the external threads with pipe compound
and draw up the connections tightly but not severely.
If a snap-acting valve (solenoid valve) is used in the
system, the snap-acting valve should be installed
upstream of the Type 75A. The Type 75A may be
damaged by high shutoff pressure if a snap-acting
valve is installed downstream.
Adjustment
One spring for each size regulator allows operation
over an outlet pressure range of 20 to 80 psi (1,4 to
5,5 bar). Maximum inlet pressure is 200 psi (13,8 bar).
Minimum operating differential pressure is 5 psi (0,34 bar).
To change the reduced pressure, loosen the adjusting
screw locknut (key 9) and turn the adjusting screw
(key 8) into the spring case to increase the reduced
pressure, or out of the case to decrease it. Re-tighten
the locknut.
W0057-1
Figure 1. Type 75A Water Pressure Regulator
Maintenance
To replace the valve disk (key 13), unscrew the guide
plug (key 3) from the body. The valve disk holder
(key 5) may now be unscrewed from the yoke (key 4). Be
careful not to twist and rupture the diaphragm (key 12).