CS800 Series
8
During normal operation the True Monitor™ is in a wide-
open state as its setpoint is set higher than the primary
regulator. See Tables 8 and 9 for guidance regarding the
setpoints of the regulator and associated Integral Monitor
sets. If the downstream pressure should rise to the setpoint
of the True Monitor due to loss of pressure control by the
primary regulator, the monitor will assume control and
regulate ow to the downstream system. If a Token relief is
present, the token relief will relieve a small amount of gas to
the atmosphere as an indication that the Integral Monitor is
controlling the downstream pressure.
Either internal or external downstream pressure registration
is available. External pressure registration requires a
downstream sensing line. See the Type TM600 Integral
True-Monitor Instruction Manual (D103126X012) for
additional details of operation.
Types CS804, CS824 and CS854
Slam-Shut Operation
The Type VSX8 Slam-shut module on the CS804 Series
regulators is a fast acting shutoff device that provides
overpressure (OPSO) or overpressure and underpressure
(OPSO/UPSO) protection by completely shutting off the ow
of gas to the downstream system. See Tables 10 and 11
for guidance regarding the typical setpoint of the regulator
and associated OPSO and UPSO sets. The Type VSX8’s
actions are independent of the CS804 Series regulator and
of variations to the inlet pressure. The Type VSX8 provides
the option of internal or external downstream pressure
registration. External registration requires a downstream
sensing line. See Figure 11 for guidance regarding
installation of the downstream control line.
The Type VSX8 shutoff disk is normally in the open (reset)
position, see Figure 5. If the downstream pressure below
the slam-shut diaphragm increases (or decreases) until
it reaches the slam-shut setpoint, this diaphragm moves
upward (or downward) to release the trip mechanism which
allows the spring force on the stem to push the disk against
the seat, shutting off all gas ow. To reset the slam-shut after
gas has been shutoff; refer to Type VSX8 Instruction Manual
(D103127X012) for additional details.
WARNING
!
In order for the Underpressure Shutoff
(UPSO) of any slam-shut to be triggered,
the downstream pipe pressure must drop
below the UPSO setpoint. In the case of a
downstream line break, numerous factors
can prevent the downstream pipe pressure
from decreasing below the slam-shut UPSO
setpoint. These factors include the distance
of pipe to the break, the diameter of the
pipe, size of the break and the number of
restrictions, such as valves, elbows and
bends, downstream of the regulator and/
or slam-shut device. Due to these factors
additional protections should be installed to
stop ow in the event of a line break.
Table 11. Regulator and Slam-Shut Underpressure Shutoff (UPSO) Pressure and Overpressure Shutoff (OPSO) Ranges
REGULATOR
SLAM-SHUT DEVICE
Under Pressure Shut-off (UPSO) Over Pressure Shut-off (OPSO)
TYPE
FACTORY
SETPOINT
SPRING
RANGE
FACTORY
SETPOINT
(1)
SPRING RANGE
SPRING PART
NUMBER AND
COLOR
FACTORY
SETPOINT
(2)
SPRING RANGE
OVER UPSO
SETPOINT
(3)
SPRING PART
NUMBER AND
COLOR
In. w.c. mbar In. w.c. mbar In. w.c. mbar In. w.c. mbar In. w.c. mbar In. w.c. mbar
CS804
7 17 5.5 to 8.5
14 to
21
3 7
2 to 12 5 to 30
T14168T0012 /
White
22 55
17 to 28 42 to 69
GF02168X012 /
Brown
11 27 8 to 12
20 to
30
6 15 25 62
14 35 10 to 16
25 to
40
9 22 30 75
1 psig 69 14 to 30
35 to
75
0.5 psig 35
0.36 to
2.3 psig
25 to
160
T14170T0012 /
Silver
2 psig 138
1.3 to
3.1 psig
90 to
214
GF02170X012 /
Orange
CS824
2 psig 138
1 to
2.5 psig
69 to
170
1 psig 69
0.36 to
2.3 psig
25 to
160
T14170T0012 /
Silver
3.5 psig 241
1.3 to
3.1 psig
90 to
214
GF02170X012 /
Orange
3 psig 207
1.5 to
3.5 psig
100 to
241
1.75 psig 121
1.5 to
7.3 psig
100 to
500
FA142869X12 /
Orange Stripe
5 psig 345
2.7 to
5.5 psig
186 to
379
GF02171X012 /
Pink
5 psig 345
2.5 to
5.5 psig
170 to
380
3 psig 207 7 psig 483
CS854 7 psig 483
5 to
10 psig
345 to
690
3.5 psig 241
1.5 to
7.3 psig
100 to
500
FA142869X12 /
Orange Stripe
9 psig 621
2.7 to
5.5 psig
186 to
379
GF02171X012 /
Pink
1. If Non-Factory UPSO setpoints are specied, a minimum differential of 4 in. w.c. / 10 mbar between UPSO setpoint and regulator setpoint must be maintained in order to ensure a
secure latch of the Slam-Shut.
2. For units equipped with Token Relief, if Non-Factory Slam-shut OPSO setpoints are specied, they must be higher than the Token Relief Start-to-Discharge values provided in Table 6.
3. If Non-Factory OPSO setpoints are specied, the allowable OPSO setpoint cannot exceed the maximum of 3 psig / 207 mbar above the regulator setpoint in order to ensure no internal
parts damage from overpressure.
Komentarze do niniejszej Instrukcji