OS2 NACE
2
MECHANISM BOX (BM)
The mechanism box is designed to close a slam shut valve. The
operation is ensured in two successive stages: a detection stage
and a power stage. The separation between the detection
stage and the power stage provides maximum precision,
indifferent of working pressure, slam shut valve diameter
and gas flow. After activation of the slam shut valve due to over
or under pressure, the mechanism box must be reset manually.
The complete system is available, on request only, sealed with
lead and wire.
SAFETY MANOMETRIC BOX (BMS)
The pressure data is transformed into a displacement by a safety
manometric box (BMS 1) mounted on the mechanism box (BM).
This displacement is used to activate the detection stage of the
mechanism box in the case of overpressure, over or
underpressure, or underpressure condition.
In certain configurations, a second box may be used (BMS 2).
1 - BM 1: Mechanism Box with
1 safety manometric box (BMS 1)
2 - BM 2: Mechanism Box with
2 safety manometric boxes (BMS 1, BMS 2)
3 - BM 1: Mechanism Box with
1 safety manometric box (BMS 1)
Bottom mounted (integrated valve and regulator)
BM 1
BMS 1
BM 2
BMS 2
BMS 1
BM 2
BMS 1
BMS 2
4 - BM 2: Mechanism Box with
2 safety manometric boxes (BMS 1, BMS 2)
N01
N02
N03
N04
TYPES OF INSTALLATION
Mounting on horizontal pipeline only:
Top mounted (stand-alone valve)
Europe, Middle East, and Africa Document Only