Emerson LMS 1000 Instrukcja Instalacji Strona 130

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 158
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 129
NetSure™ LMS Data Processing Unit
Installation Instructions, Section 5879 (Issue BA, April 7, 2014)
Spec. No: 58650500, 586505500 Code: Section 5879
Model No: LMS1000 Issue BA, April 7, 2014
[122 of 149]
CONFIG A_
Off Delay Time:
Type the required alarm off delay time period* and a modifier*, then
press
ENTER
. The off delay time is the amount of seconds that an alarm
condition must cease before the system recognizes that the alarm
condition ceased.
* Enter a valid value (0-9999) then the modifier (s for seconds, m for
minutes, h for hours). If no modifier entered, modifier defaults to
seconds.
On Delay Time:
Type the required alarm on delay time period* and a modifier*, then
press
ENTER
. The on delay time is the amount of seconds that an alarm
condition must exist before the system recognizes it as an alarm
condition.
* Enter a valid value (0-9999) then the modifier (s for seconds, m for
minutes, h for hours). If no modifier entered, modifier defaults to
seconds.
Save changes (Y or N):
Type
Y
if the above entered data is to be saved in the current analog
configuration file and
N
if not, then press
ENTER
.
Przeglądanie stron 129
1 2 ... 125 126 127 128 129 130 131 132 133 134 135 ... 157 158

Komentarze do niniejszej Instrukcji

Brak uwag