8 • XEV22D I&O Manual 026-1206 Rev 0 09-FEB-2011
8 Parameters
NOTE: All pressure parameters are relatives or absolutes depending on the PrM parameter.
Code Description Function
REGULATION
Fty Kind of gas (R22, 134, 404, 407, 410, 507, CO2)
Type of gas used by plant. Fundamental parameter for correct function-
ing of all systems.
PEo Probe error opening percentage (0 to 100%)
If a temporary probe error occurs, valve opening percentage is PEo until
PEd time is elapsed. If PEo is different from 0, it ensures cooling also
with probe error, because even if the device cannot calculate superheat,
the valve can work at PEo percentage.
PEd Probe error delay before stopping
regulation
(0 to 239 sec – 240 = On = unlimited)
If the probe error duration is bigger than PEd, valve closes completely.
The Pf message is displayed. If PEd = On, valve opening is PEo until
probe error finishes.
tEU Type of stepper motor (uP- bP)
Selects the kind of valve.
uP = 5 to 6 wires unipolar valves
bP = 4 wires bipolar valves
CAUTION!
By changing this parameter, the valve has to be re-initial-
ized.
tEP Predefined valve selection (0 to 10)
If tEP = 0, the user has to configure all the parameters to use the valve.
If tEP
is different from 0, the controller performs a fast configuration of
the following parameters: LSt, Ust, Sr, CPP, and CHd. To select the
correct value, refer to Table 4-1.
If tEP
is different from 0, previous configuration of LSt, Ust, Sr, CPP,
and CHd are overwritten
.
LSt Minimum number of steps (0 to Ust)
Selects the minimum number of steps. At this number of steps, the valve
should be closed. Read the manufacturer datasheet to set this parameter
correctly. The number of steps should be set within the advised range of
functioning.
CAUTION!
When this parameter is changed, the valve must be re-ini-
tialized.The controller performs this procedure automatically and re-
starts its normal functioning when the programming mode ends.
Ust Maximum number of steps (LSt to 800*10)
Selects the maximum number of steps. At this number of steps, the valve
should be opened completely. Read the datasheet provided by the valve
manufacturer to set this parameter correctly. The maximum number of
steps should be set within the advised range of functioning.
CAUTION!
When this parameter is changed, the valve must be re-ini-
tialized.The controller performs this procedure automatically and re-
starts its normal functioning when the programming mode ends.
Table 8-1 - List of Parameters