20 • XEV22D I&O Manual 026-1206 Rev 0 09-FEB-2011
5. Four fields will become visible underneath the
COM port connection field, which pertain to the
way the device communicates:
• Baud - Default setting is 19.2k. The baud rate set-
ting should be set to match the baud rate of the de-
vice (9600). (All devices connected to the same
COM port should be set to the same baud rate.)
• Data Size - Leave this field at the default value (8).
• Parity - Leave this field at the default value (None).
• Stop Bits - Leave this field at the default value (1).
6. Press
to save changes and exit.
17.1.2.Add and Connect the Device
To enable communications between E2 and the
units, the devices must be added and addressed in E2.
1. Log in to the E2 with Level 4 access.
2. Press
- Connected I/O Boards
and Controllers.
3. In the Num Network Ctrls: NetSetup screen, under
the ECT tab, enter the number of devices in the
Quantity field. (Max shows the maximum number
of devices allowed on the network.)
4. Press
to return to the Network Setup menu,
then select
- Network Summary.
5. Locate the units you added to the network list (press
and to scroll through the list). If desired, en-
ter a new name for each device in the Name field.
6. By default, each device in the network list has a
board number of 0. To set the address and begin
communication, choose the device and press
. In the list of MODBUS devices, choose the
address number corresponding to the address set up
through the front display, and press
to select
it. A window will open where you can specify the
address of the controller. If a network ID has al-
ready been selected, its name will be shown next to
the network ID in this list. If the network ID you are
trying to assign has already been used, you must set
the address on this device to a different number that
is not being used.
7. Repeat Steps 5 and 6 until each device has a name
and address.
8. When finished, press
to return to the Net-
Figure 17-4 - Num Network Ctrls: NetSetup Screen
Figure 17-5 - Network Summary Screen
Figure 17-6 - List of MODBUS Devices