16 • XEV22D I&O Manual 026-1206 Rev 0 09-FEB-2011
14 Display Messages
14.1.Alarm Recovery
Probe alarms P1 and P2 start a few seconds after
the fault in the probe; they automatically stop few sec-
onds after the probe restarts normal operation. Check
the connections before replacing the probe. Maxi-
mum and minimum alarms HSH, LSH, MOP, and
LOP automatically stop as soon as the variable re-
turns to normal values.
The controller is provided with an internal check
to verify memory integrity. Alarm EE flashes when a
failure in the internal memory is detected. In this case,
call for service.
Message Cause Outputs
nA None of the digi-
tal inputs config-
ured as CCL are
activated
Valve closed
Pf The PEd time is
elapsed and the
regulation is
stopped.
Valve closed after
PEd. There is a probe
error.
P1 Temperature
probe fault
According to PEo
and PEd
P2 Pressure transduc-
er fault
According to PEo
and PEd
HSH High superheat
alarm
By PI
LSH Low superheat
alarm
Valve closed
LPL Low pressure lim-
it
See LPL parameter
MOP Maximum Oper-
ating Pressure
See dML parameter
LOP Lowest Operat-
ing Pressure
See dML parameter
StF Start Function en-
abled
See SFd parameter
StP Regulation stop
caused by Std and
Sti
Valve closed
EE Memory anomaly
Table 14-1 - Alarm Signals