Europe,
Middle
East,
and
Africa
Document
Only
Types EZH and EZHSO
11
Figure 12. Type EZHSO DN 100 (Spring-to-Open Version) Operational Schematic
Inlet pressure (Pu)
Outlet pressure (Pd)
Motorization pressure (Pm)
Pilot feeding pressure (Pup)
Atmospheric pressure (Pb)
V
M
R
S
B
L
A
R2
R3
RP IP
R4
MONITORING SYSTEMS
Monitoring regulation is overpressure protection by
containment, therefore, there is no relief valve to vent to the
atmosphere. When the working regulator fails to control
the pressure, a monitor regulator installed in series, which
has been sensing the downstream and control pressure,
goes into operation to maintain the downstream pressure
at a slightly higher level than normal pressure. During an
overpressure situation, the monitoring system keeps the
customer on line.
Also testing is relatively easy and safe. To perform a
periodic test on a monitoring regulator, increase the outlet
set pressure of the working regulator and watch the outlet
pressure to determine if the monitoring regulator takes over
at the appropriate outlet pressure.
Wide-Open Monitoring Systems
In normal operation of a wide-open conguration, the
working regulator controls the system’s outlet pressure.
With a higher outlet pressure setting, the monitor regulator
senses a pressure lower than its setpoint and tries to
increase outlet pressure by going wide open. If the working
regulator fails, the monitoring regulator assumes control and
holds the outlet pressure at its outlet pressure setting.
Figure 13 shows an upstream wide-open monitor Type EZH
(Spring-to-Close) and a downstream active regulator
Type EZHSO (Spring-to-Open). With this conguration,
in case of regulator main diaphragm failure, it will fail in
open position letting the monitor work properly; in case
of monitor main diaphragm failure, it will fail in close
position guaranteeing a protection against overpressure to
downstream system.
TYPE PRX:
S - BLEED PORT TYPE SA/2
B - SUPPLY PORT V - SENSING
L - MOTORIZATION PORT R - PILOT
A - SENSING PORT M - INLET