XD Overhead Cooling Module—Liebert XDO
36
4.4 Liebert XDC Standard Features
Compressors—Scroll with a suction gas cooled motor, vibration isolators, thermal overloads, man-
ual reset high-pressure switch and pump down low-pressure switch.
Refrigeration System—Dual refrigeration circuits each including liquid line filter dryers, refriger-
ant sight glass with moisture indicator, electronic control valve, adjustable externally equalized
expansion valves and liquid line solenoid valves.
Heat Exchanger—Brazed plate design with interwoven circuiting constructed of stainless steel
plates, copper brazed. PUMPS Centrifugal type, end suction, canned rotor design.
Standard Control Processor—The standard control system is microprocessor-based with an exter-
nal LCD numerical display to allow observation of specified adjustable functions. Normal operat-
ing conditions are indicated on the LCD panel, which is mounted either on the unit or on the wall,
depending on application details (see user manual, SL-16671). The control system also monitors
unit operation and activates an alarm when any of the specified factory preset conditions are
exceeded.
Cabinet and Frame—Custom powder painted steel panels. A hinged control access panel opens to
a second front panel, which is a protected enclosure for all high voltage components. Frame is con-
structed of 14 gauge heliarc welded tubular steel and painted using an auto-deposition coating
system.
Figure 37 XDC dimensional data
74" (1880mm)
Overall
34-5/8"
(879mm)
Overall
72"
(1829mm)
Unit Base
33"
(838mm)
Unit Base
33"
(838mm)