XD Overhead Cooling Module—Liebert XDO
36
4.4 Liebert XDC Standard Features
• Compressors—Scroll with a suction gas cooled motor, vibration isolators, thermal overloads, man-
ual reset high-pressure switch and pump down low-pressure switch.
• Refrigeration System—Dual refrigeration circuits each including liquid line filter dryers, refriger-
ant sight glass with moisture indicator, electronic control valve, adjustable externally equalized
expansion valves and liquid line solenoid valves.
• Heat Exchanger—Brazed plate design with interwoven circuiting constructed of stainless steel
plates, copper brazed. PUMPS Centrifugal type, end suction, canned rotor design.
• Standard Control Processor—The standard control system is microprocessor-based with an exter-
nal LCD numerical display to allow observation of specified adjustable functions. Normal operat-
ing conditions are indicated on the LCD panel, which is mounted either on the unit or on the wall,
depending on application details (see user manual, SL-16671). The control system also monitors
unit operation and activates an alarm when any of the specified factory preset conditions are
exceeded.
• Cabinet and Frame—Custom powder painted steel panels. A hinged control access panel opens to
a second front panel, which is a protected enclosure for all high voltage components. Frame is con-
structed of 14 gauge heliarc welded tubular steel and painted using an auto-deposition coating
system.
Figure 37 XDC dimensional data
74" (1880mm)
Overall
34-5/8"
(879mm)
Overall
72"
(1829mm)
Unit Base
33"
(838mm)
Unit Base
33"
(838mm)