System Description
2
1.1 Direct and Indirect System Configurations
Liebert XD systems are available in Direct and Indirect configurations—differentiated essentially
by the location of the pumping unit (see Figures 2 and 3). The indirect system uses a pumping unit
to control and circulate the XD Coolant™. In the direct system, the pumping functions are incorpo-
rated in the chiller.
Figure 2 Direct system configuration—hydraulic system schematic
Figure 3 Indirect system configuration—hydraulic system schematic
1.2 Liebert XDO—Overhead Cooling Module
The XDO ceiling-mounted cooling module draws in hot air rising from densely populated cabinets,
passes it over the XDO’s coils and exhausts cooled air downward into the cold aisle.
Liebert
XDC Coolant
Chiller
XDO/XDV
XDO/XDV
XDO/XDV
XDO/XDV
XDCoolant
XDCoolant
Liebert
Heat
Rejection
Liebert
XDC Coolant
Chiller
Direct XD System Configuration
Pumping and control are performed by chiller.
Supply Piping
Return Piping
Liebert
XDP
XDO/XDV
XDO/XDV
XDCoolant
Building
Chilled
Water
Liebert
XDP
XDO/XDV
XDCoolant
Indirect XD
System Configuration
XDPs pump coolant to XDO and XDV
modules, isolate coolant from building
chilled water supply with an internal
heat exchanger and maintains coolant
above the dew point.
Supply Piping
Return Piping