4 • XEV22D I&O Manual 026-1206 Rev 3 13-DEC-2012
5 Mounting and
Powering
The XEV22D is usually mounted by the Refriger-
ation equipment manufacturer. Therefore, the install-
er need only make the necessary connections between
the boards and the site controller(s).
In some instances, an installer may be required to
mount the XEV22D. There are no restrictions on the
location of the XEV22D; however, the controller
should be mounted in a location protected from mois-
ture. Typically, mounting inside the electrical control
panel of a package unit is acceptable.
5.1. Installation
The XEV22D uses a DIN mount installation.
5.2. Powering the XEV22D
Retail Solutions supplies a wide variety of 24VAC
transformers with varying sizes without center taps.
Table 5-2 shows the transformer sizes and are non
center-tapped.
5.2.1. Choosing Transformer Sizes
The transformer used to power the XEV22D
should have at least a 20VA rating. The XEV22D
should not share a transformer with any other de-
vices.
Figure 5-1 - DIN Mounting
Mount: On a DIN rail (EN 50022,
DIN 43880) Fastened with
screws via the removable
plastic flaps
Material: PC-ABS Thermoplastic
Self-extinguishing: VO (UL94)
Comparative Tracking
Index (CTI):
300V
Color: Gray
Table 5-1- XEV22D Enclosure Specification