Alarm Recovery Display Messages • 19
16 Display Messages
16.1.Alarm Recovery
Probe alarms P1 and P2 start a few seconds after
the fault in the probe; they automatically stop few sec-
onds after the probe restarts normal operation. Check
the connections before replacing the probe. Maxi-
mum and minimum alarms HSH, LSH, MoP, and
LoP automatically stop as soon as the variable returns
to normal values.
The controller is provided with an internal check
to verify memory integrity. Alarm EE flashes when a
failure in the internal memory is detected. In this case,
call for service.
Message Cause Outputs
nA None of the digital in-
puts configured as
CCL are activated
Valve closed
Pf The PEd time is
elapsed and the regu-
lation is stopped.
Valve closed after
PEd. There is a
probe error.
P1 Temperature probe
fault
According to PEo
and PEd
P2 Pressure transducer
fault
According to PEo
and PEd
HSH High superheat alarm By PI
LSH Low superheat alarm Valve closed
LPL Low pressure limit See LPL parame-
ter
MoP Maximum Operating
Pressure
See dML parame-
ter
LoP Lowest Operating
Pressure
See dML parame-
ter
StF Start Function en-
abled
See SFd parameter
StP Regulation stop
caused by Std and Sti
Valve closed
EE Memory anomaly
Table 16-1 - Alarm Signals