26 • XEV22D I&O Manual 026-1206 Rev 3 13-DEC-2012
20 Standard Values
NOTE: For viewing and adjusting setpoints, refer to: Section 9.2., To See the Setpoint and Section 9.3., To
Modify the Setpoint.
Label Description Range Default Level
Fty Kind of gas R22, 134, 404, 407, 410, 507, CO2 404 Pr2
PEo Probe error opening percentage 0 to 100% 50 Pr2
PEd Probe error delay before stopping regulation 0 to 239 sec - On On Pr2
tEU Type of stepper motor uPbP bP Pr2
tEP Automatic valve configuration 0 to 10 1 Pr2
LSt Minimum number of steps 0 – Ust See tEP Pr2
Ust Maximum number of steps LSt – 800 * 10 See tEP Pr2
Sr Step rate 10 to 600 step/s See tEP Pr2
CPP Current per phase (only bipolar valves) 0 to 100 * 10mA See tEP Pr2
CHd Holding current per phase (only bipolar valves) 0 to 100 * 10mA See tEP Pr2
oPE Start opening percentage 0 to 100% 85 Pr2
SFd Start function duration 0.0 to 42.0 min: tens of seconds 1.3 Pr2
Sti Stop regulation interval 0.0 to 24.0 hr: tens of minutes 0 Pr2
Std Stop duration 0 to 60 min 0 Pr2
MnF Maximum opening percentage 0 to 100% 100 Pr2
FOP Forced opening time-out 0 to 100% - not used not used Pr2
PI PARAMETERS (For trained staff use only)
Pb Proportional band 0.1 to 50.0°C/ 1 to 90°F 10.0 Pr2
rS Band offset -12.0 to 12.0°C/ -21 to 21°F 0.0 Pr2
inC Integration time 0 to 255 sec 120 Pr2
PROBE PARAMETERS
tPP Type of pressure transducer 420 - 5V- LAn 420 Pr2
LPP Enable pressure probe sending in LAN n to YnPr2
PA4 Probe value at 4mA or at 0V
(related to PrM parameter)
-1.0 bar/ -14 PSI -0.5 Pr2
P20 Probe value at 20mA or at 5V
(related to PrM parameter)
PA4 to 50.0 bar/ 725 PSI 11.0 Pr2
OPr Pressure probe calibration -12.0 to 12.0 bar/ -174 to 174 psi 0 Pr2
ttE Type of temperature probe PtM to ntC PtM Pr2
otE Temperature probe calibration -12.0 to 12.0°C/ -21 to 21°F 0 Pr2
DIGITAL INPUTS
Table 20-1 - XEV22D Standard Parameter Values
Przeglądanie stron 31