Liebert® IntelliSlot® Modbus RTU, Modbus TCP, BACnet MSTP andBACnet IPReference Guide

Strona 2

Liebert Equipment Compatibility - Compatibility with Liebert EquipmentLiebert® IntelliSlot® Modbus/BACnet 4• Battery Monitoring ProductsAlber BDSU™78-

Strona 3 - TABLE OF CONTENTS

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 94Table 27 Liebert Challenger 3000™, Liebert Delu

Strona 4

Modbus RTU and Modbus TCP Protocols - Thermal Management Products95 Liebert® IntelliSlot® Modbus/BACnetInverter on Bypass — 40291 1 — Bit 3Standby Fan

Strona 5

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 96Table 28 Liebert DataMate™, Liebert Mini-Mate P

Strona 6

Modbus RTU and Modbus TCP Protocols - Thermal Management Products97 Liebert® IntelliSlot® Modbus/BACnetTable 29 Liebert DataMate™, Liebert Mini-Mate2™

Strona 7 - MSTP or BACnet IP

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 98Setpoints (View)Temperature — 40010 1 — —Temp T

Strona 8 - Modbus/BACnet 2

Modbus RTU and Modbus TCP Protocols - Thermal Management Products99 Liebert® IntelliSlot® Modbus/BACnetTable 30 Liebert Mini-Mate2™ 8 Ton - Input and

Strona 9 - 3Liebert

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 100Run Times (View)Compressor 1 Run Hours — 40019

Strona 10 - Modbus/BACnet 4

Modbus RTU and Modbus TCP Protocols - Thermal Management Products101 Liebert® IntelliSlot® Modbus/BACnetTable 31 Liebert Atlas Air™, Liebert Atlas PEC

Strona 11 - 2.0 MODBUS COMMUNICATIONS

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 102Setpoints (View)Return Air Temperature — 40016

Strona 12 - 2.4 RTU Framing

Modbus RTU and Modbus TCP Protocols - Thermal Management Products103 Liebert® IntelliSlot® Modbus/BACnetTable 32 Liebert Atlas Air™, Liebert Atlas PEC

Strona 13

Modbus Communications - Implementation Basics5Liebert® IntelliSlot® Modbus/BACnet2.0 MODBUS COMMUNICATIONS2.1 Implementation BasicsModbus protocol pro

Strona 14

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 104Humidity Low Level — 40290 1 — Bit 4Battery Le

Strona 15

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products105 Liebert® IntelliSlot® Modbus/BACnet3.2 Power Distribution

Strona 16

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 106Alarm PointsDiscrete al

Strona 17

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products107 Liebert® IntelliSlot® Modbus/BACnetTable 34 Liebert Datawa

Strona 18

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 108Table 35 Liebert FPC™,

Strona 19

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products109 Liebert® IntelliSlot® Modbus/BACnetPanel 4Panel Summary Al

Strona 20

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 110Panel 4 Position 1Branc

Strona 21

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products111 Liebert® IntelliSlot® Modbus/BACnetTable 36 Liebert FPC™,

Strona 22

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 112Output Power 2 (used on

Strona 23

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products113 Liebert® IntelliSlot® Modbus/BACnetPanel Main Current Ix 3

Strona 24

Modbus Communications - RTU FramingLiebert® IntelliSlot® Modbus/BACnet 62.3.2 Function CodeThe function code field tells the addressed slaves what fun

Strona 25

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 114Panel Main Voltage Vy T

Strona 26

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products115 Liebert® IntelliSlot® Modbus/BACnetPanel 1 Position 1Break

Strona 27

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 116Panel 2 Position 2Break

Strona 28

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products117 Liebert® IntelliSlot® Modbus/BACnetPanel 3 Position 84Brea

Strona 29

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 118Subfeed 1Subfeed Curren

Strona 30

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products119 Liebert® IntelliSlot® Modbus/BACnetSubfeed 64Subfeed Curre

Strona 31

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 120Table 37 Liebert EXC™,

Strona 32

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products121 Liebert® IntelliSlot® Modbus/BACnetPanel 2 Position 1Branc

Strona 33

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 122Subfeed 1Subfeed Phase

Strona 34

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products123 Liebert® IntelliSlot® Modbus/BACnetTable 38 Liebert EXC™,

Strona 35

Modbus RTU and Modbus TCP Protocols - Thermal Management Products7Liebert® IntelliSlot® Modbus/BACnet3.0 MODBUS RTU AND MODBUS TCP PROTOCOLS3.1 Ther

Strona 36

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 124Panel Main Current Iy 3

Strona 37

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products125 Liebert® IntelliSlot® Modbus/BACnetPanel Main Voltage Vy T

Strona 38 - Modbus/BACnet 32

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 126Panel 2 Position 1Break

Strona 39

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products127 Liebert® IntelliSlot® Modbus/BACnetPanel 3 Position 2Break

Strona 40

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 128Panel 4 Position 84Brea

Strona 41

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products129 Liebert® IntelliSlot® Modbus/BACnetSubfeed Current Iy THD

Strona 42

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 130Table 39 Liebert FDC™,

Strona 43

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products131 Liebert® IntelliSlot® Modbus/BACnetTable 40 Liebert FDC™,

Strona 44

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 132Panel Main Output Perce

Strona 45

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products133 Liebert® IntelliSlot® Modbus/BACnetTable 41 Liebert EXC™,

Strona 46

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 8Compressor Thermal Overload 2 10043 — 1 Active

Strona 47

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 134Output Undervoltage Uni

Strona 48

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products135 Liebert® IntelliSlot® Modbus/BACnetPhase Loss Voltage and/

Strona 49

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 136Table 42 Liebert® STS™,

Strona 50

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products137 Liebert® IntelliSlot® Modbus/BACnetSource 2 Overload — 402

Strona 51

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 138Table 43 Liebert® STS2™

Strona 52

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products139 Liebert® IntelliSlot® Modbus/BACnetLoadKVA % — 40026 1 — %

Strona 53

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 140Internal Comm Fail — 40

Strona 54 - Table 11 Liebert CRV

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products141 Liebert® IntelliSlot® Modbus/BACnetLoad Over-current — 402

Strona 55 - 49 Liebert

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 1423.3 UPS SystemsTable 44 Liebert APM™, Liebert NXC™, Liebert NX

Strona 56 - Table 12 Liebert CRV

Modbus RTU and Modbus TCP Protocols - UPS Systems143 Liebert® IntelliSlot® Modbus/BACnetUser Operation Invalid 10050 — 1 — Active on AlarmPower Sub Mo

Strona 57 - 51 Liebert

Modbus RTU and Modbus TCP Protocols - Thermal Management Products9Liebert® IntelliSlot® Modbus/BACnetFree Cooling Valve Hours Exceeded 10083 — 1 Act

Strona 58 - Modbus/BACnet 52

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 144OutputSystem Output Voltage RMS A-N 30419 — 1 — VACSystem Outp

Strona 59 - 53 Liebert

Modbus RTU and Modbus TCP Protocols - UPS Systems145 Liebert® IntelliSlot® Modbus/BACnetTable 46 Liebert APM™, Liebert NXC™, Liebert NXR™ - GlossaryDa

Strona 60 - Table 13 Liebert CRV

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 146Load Sharing Fault Difference between any phase inverter curre

Strona 61 - 55 Liebert

Modbus RTU and Modbus TCP Protocols - UPS Systems147 Liebert® IntelliSlot® Modbus/BACnetSystem Output Power Factor Phs B The system output power fact

Strona 62 - Modbus/BACnet 56

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 148OutputOutput Overload 10050 — 1 Active on AlarmOutput Off Pen

Strona 63 - 57 Liebert

Modbus RTU and Modbus TCP Protocols - UPS Systems149 Liebert® IntelliSlot® Modbus/BACnetTable 48 Liebert APS™ - Input and HoldingData LabelInputRegist

Strona 64 - (Chiller) - Status and Coil

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 150BatteryBattery Time Remaining 30437 — 1 —Units : min Uint 16B

Strona 65 - 59 Liebert

Modbus RTU and Modbus TCP Protocols - UPS Systems151 Liebert® IntelliSlot® Modbus/BACnetSystem Output Apparent Power L1 30473 — 1 100 Units : kVA Uin

Strona 66 - Table 15 Liebert HPC

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 152Auto Restart — — 40519 1 0 = disabled 1 = enabled Auto Restar

Strona 67 - 61 Liebert

Modbus RTU and Modbus TCP Protocols - UPS Systems153 Liebert® IntelliSlot® Modbus/BACnetBatteryModule 2Module Operating Status 30670 — 1 —0 = Normal

Strona 68 - Modbus/BACnet 62

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 10Digital Output Board Not Detected 1 10224 — 1

Strona 69 - 63 Liebert

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 154Table 49 Liebert APS™ - GlossaryData Label Data DescriptionAcc

Strona 70

Modbus RTU and Modbus TCP Protocols - UPS Systems155 Liebert® IntelliSlot® Modbus/BACnetFrame Capacity Total system capacity supported when the maximu

Strona 71 - Table 17 Liebert HPC

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 156Output Qualification Status output qualification status Power

Strona 72 - Modbus/BACnet 66

Modbus RTU and Modbus TCP Protocols - UPS Systems157 Liebert® IntelliSlot® Modbus/BACnetSystem Output Power L2 The system output power on Line 2. Sys

Strona 73 - Table 18 Liebert XDC

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 158Table 50 Liebert GXT2™ and Liebert GXT3™ - Status and CoilData

Strona 74 - Table 19 Liebert XDC

Modbus RTU and Modbus TCP Protocols - UPS Systems159 Liebert® IntelliSlot® Modbus/BACnetTable 51 Liebert GXT2™ and Liebert GXT3™ - Input and HoldingDa

Strona 75 - 69 Liebert

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 160Output Current L1 30164 — 1 — AInput Maximum Voltage L1 30180

Strona 76 - Table 20 Liebert XDP

Modbus RTU and Modbus TCP Protocols - UPS Systems161 Liebert® IntelliSlot® Modbus/BACnetTable 54 Liebert Nfinity® - Status and CoilData DescriptionSta

Strona 77 - 71 Liebert

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 162Table 55 Liebert Nfinity® - Input and HoldingData DescriptionI

Strona 78 - Table 21 Liebert XDP

Modbus RTU and Modbus TCP Protocols - UPS Systems163 Liebert® IntelliSlot® Modbus/BACnetTable 56 Liebert NX™ - Status and CoilData DescriptionStatus C

Strona 79 - 73 Liebert

Modbus RTU and Modbus TCP Protocols - Thermal Management Products11 Liebert® IntelliSlot® Modbus/BACnetRemote Sensor Over Temperature 1 10356 — 1 Ac

Strona 80 - Modbus/BACnet 74

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 164DC Bus Balancer Fault 10240 — — — —DC Bus 1 Power Supply Fail

Strona 81 - 75 Liebert

Modbus RTU and Modbus TCP Protocols - UPS Systems165 Liebert® IntelliSlot® Modbus/BACnetTable 57 Liebert NX™ - Input and HoldingData DescriptionInputR

Strona 82 - Modbus/BACnet 76

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 166Input Current L1 30154 — 1 — AInput Power Factor L1 30155 — 1

Strona 83 - 77 Liebert

Modbus RTU and Modbus TCP Protocols - UPS Systems167 Liebert® IntelliSlot® Modbus/BACnetTable 58 Liebert NX 225-600kVA UPS - Input and Holding3Data De

Strona 84 - Modbus/BACnet 78

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 168OutputSource — 40050 1 —1 = Other2 = None3 = Normal4 = Bypass5

Strona 85 - 79 Liebert

Modbus RTU and Modbus TCP Protocols - UPS Systems169 Liebert® IntelliSlot® Modbus/BACnetDiagnostic Test Failed — 40089 1 — Bit 3Communications Lost —

Strona 86 - Modbus/BACnet 80

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 170Table 59 Liebert NXL™ - 60Hz, UL version (Model 40) - Status a

Strona 87 - 81 Liebert

Modbus RTU and Modbus TCP Protocols - UPS Systems171 Liebert® IntelliSlot® Modbus/BACnetBattery Over Temperature 10350 — 1 Active on Warning N+1, 1+N,

Strona 88 - Modbus/BACnet 82

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 172Controls Reset Required 10397 — 1 Active on Alarm SCC, N+1, 1+

Strona 89 - Table 22 Liebert XDP

Modbus RTU and Modbus TCP Protocols - UPS Systems173 Liebert® IntelliSlot® Modbus/BACnetTable 60 Liebert NXL™ - 60Hz, UL version (Model 40) - Input an

Strona 90 - Modbus/BACnet 84

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 12EEV Unspecified General Event 10488 — 1 Activ

Strona 91 - 85 Liebert

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 174System Output Pct Power Phase A 30165 — 1 — %N+1, 1+N,1+1, SMS

Strona 92

Modbus RTU and Modbus TCP Protocols - UPS Systems175 Liebert® IntelliSlot® Modbus/BACnetBattery Total Discharge Time 30316 — 1 — hrN+1, 1+N,1+1, SMSBa

Strona 93

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 176Rectifier Active Filter 30340 — 1 —0 = Not Installed1 = Instal

Strona 94

Modbus RTU and Modbus TCP Protocols - UPS Systems177 Liebert® IntelliSlot® Modbus/BACnetBattery Volts for Cabinet 4 30361 — 1 — VDCN+1, 1+N,1+1, SMSBa

Strona 95

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 178Maintenance Isolation Breaker (MIB)30383 — 1 —0 = Open1 = Clos

Strona 96

Modbus RTU and Modbus TCP Protocols - UPS Systems179 Liebert® IntelliSlot® Modbus/BACnetConfiguration Description 30497 — 1 —0 = Single Module System

Strona 97

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 180Sum of MMS Output RMS Currents for Phase B30512 — 1 — Units :

Strona 98 - Table 25 Liebert XDF

Modbus RTU and Modbus TCP Protocols - UPS Systems181 Liebert® IntelliSlot® Modbus/BACnetBypass Isolation Breaker forModule 1 (BIB1)30537 — 1 —0 = Open

Strona 99 - Table 26 Liebert XDF

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 182MMS Module Output VoltageStatus30557 — 1 —0 = Fail1 = Marginal

Strona 100

Modbus RTU and Modbus TCP Protocols - UPS Systems183 Liebert® IntelliSlot® Modbus/BACnetMMS Module Total kVA Output 30651 — 1 — Units : kVA SCCMMS Mod

Strona 101

Modbus RTU and Modbus TCP Protocols - Thermal Management Products13 Liebert® IntelliSlot® Modbus/BACnetExternal Condenser TVSS Issue 10655 — 1 Activ

Strona 102

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 184EcoModeSchedule 2Schedule Operation State - ECO Mode30682 — 1

Strona 103

Modbus RTU and Modbus TCP Protocols - UPS Systems185 Liebert® IntelliSlot® Modbus/BACnetTable 61 Liebert NXL™ - 60Hz, UL version (Model 40) - Glossary

Strona 104

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 186Battery Total Discharge Time The cumulative battery discharge

Strona 105 - Alarm Points

Modbus RTU and Modbus TCP Protocols - UPS Systems187 Liebert® IntelliSlot® Modbus/BACnetInlet Air Temperature The temperature of the inlet air Input

Strona 106 - Table 30 Liebert Mini-Mate2

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 188Multiple Fan Failure Multiple fan failure On Generator A gen

Strona 107

Modbus RTU and Modbus TCP Protocols - UPS Systems189 Liebert® IntelliSlot® Modbus/BACnetSystem Input RMS Current Phase C The system input RMS current

Strona 108

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 190Table 62 Liebert NXL™ - 50Hz, CE version (Models 48 and 49) -

Strona 109

Modbus RTU and Modbus TCP Protocols - UPS Systems191 Liebert® IntelliSlot® Modbus/BACnetDC BusDC Bus Low Fault 10074 — 1 Active on AlarmOutputSystem S

Strona 110

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 192Internal Communications Failure 10176 — 1 Active on AlarmUPS O

Strona 111

Modbus RTU and Modbus TCP Protocols - UPS Systems193 Liebert® IntelliSlot® Modbus/BACnetTable 63 Liebert NXL™ - 50Hz, CE version (Models 48 and 49) -

Strona 113

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 14Condenser Fan Issue 1 10723 — 1 Active on Ala

Strona 114

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 194Battery Volts for Cabinet 4 30428 — 1 —Units : VDCUint16Batter

Strona 115

Modbus RTU and Modbus TCP Protocols - UPS Systems195 Liebert® IntelliSlot® Modbus/BACnetDC BusDC Bus Voltage 30465 — 1 —Units : VDCUint16DC Bus Curren

Strona 116

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 196InverterInverter Overload Time Remaining 30510 — 1 —Units : se

Strona 117

Modbus RTU and Modbus TCP Protocols - UPS Systems197 Liebert® IntelliSlot® Modbus/BACnetOutput Wire Configuration 30556 — 1 —0 = Two Wire (single phas

Strona 118

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 198RatingsBypass Nominal Voltage 30576 — 1 —Units : VACUint16Syst

Strona 119

Modbus RTU and Modbus TCP Protocols - UPS Systems199 Liebert® IntelliSlot® Modbus/BACnetModule Output Breaker 30609 — 1 —0 = Open1 = Close2 = Not Inst

Strona 120

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 200Module Output Breaker for Module 3 30646 — 1 —0 = Open1 = Clos

Strona 121

Modbus RTU and Modbus TCP Protocols - UPS Systems201 Liebert® IntelliSlot® Modbus/BACnetMMS UPS Output Source 30665 — 1 —1 = Other2 = Off3 = Normal4 =

Strona 122

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 202Intelligent ParallelingIntelligent Parallel Operation State 30

Strona 123

Modbus RTU and Modbus TCP Protocols - UPS Systems203 Liebert® IntelliSlot® Modbus/BACnetEcoModeSchedule 14Schedule Operation State - ECO Mode 31019 —

Strona 124

Modbus RTU and Modbus TCP Protocols - Thermal Management Products15 Liebert® IntelliSlot® Modbus/BACnetTable 8 Liebert Challenger 3000™, Liebert Chall

Strona 125

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 204Table 64 Liebert NXL™ - 50Hz, CE version (Models 48 and 49) -

Strona 126

Modbus RTU and Modbus TCP Protocols - UPS Systems205 Liebert® IntelliSlot® Modbus/BACnetBattery Time Remaining The calculated available time on batter

Strona 127

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 206DC Bus VoltageThe voltage between the positive and negative te

Strona 128

Modbus RTU and Modbus TCP Protocols - UPS Systems207 Liebert® IntelliSlot® Modbus/BACnetInverter Overload Phase B Inverter is operating with an overlo

Strona 129

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 208MMS Output Power The sum total power of all system output modu

Strona 130

Modbus RTU and Modbus TCP Protocols - UPS Systems209 Liebert® IntelliSlot® Modbus/BACnetProgram Input Contact 04When the signal from [Program Input Co

Strona 131

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 210Sum of MMS Output RMS Currents for Phase CThe sum of the multi

Strona 132

Modbus RTU and Modbus TCP Protocols - UPS Systems211 Liebert® IntelliSlot® Modbus/BACnetSystem Output Power The sum total power of all system output p

Strona 133

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 212Table 65 Liebert PowerSure™ Interactive (before July 2008) - S

Strona 134

Modbus RTU and Modbus TCP Protocols - UPS Systems213 Liebert® IntelliSlot® Modbus/BACnetTable 66 Liebert PowerSure™ Interactive (before July 2008) - I

Strona 135

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 16Return Air Over Temp Threshold 30739 40739 1 10

Strona 136 - Modbus/BACnet 130

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 214Table 67 Liebert PowerSure™ Interactive 2 - Status and CoilApp

Strona 137

Modbus RTU and Modbus TCP Protocols - UPS Systems215 Liebert® IntelliSlot® Modbus/BACnetTable 68 Liebert PowerSure™ Interactive 2 - Input and HoldingA

Strona 138

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 216Table 69 Liebert Series 300™ UPS - Status and CoilData Descrip

Strona 139

Modbus RTU and Modbus TCP Protocols - UPS Systems217 Liebert® IntelliSlot® Modbus/BACnetTable 70 Liebert Series 300™ UPS - Input and HoldingData Descr

Strona 140

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 218Bypass Current L2 30210 — 1 — AOutput Voltage L2 30213 — 1 — V

Strona 141

Modbus RTU and Modbus TCP Protocols - UPS Systems219 Liebert® IntelliSlot® Modbus/BACnetTable 71 Liebert Series 600™ UPS - Status and CoilData Descrip

Strona 142

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 220Table 72 Liebert Series 600™ UPS - Input and HoldingData Descr

Strona 143

Modbus RTU and Modbus TCP Protocols - UPS Systems221 Liebert® IntelliSlot® Modbus/BACnetTable 73 Liebert Series 610™ SCC UPS - Status and CoilData Des

Strona 144

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 222Table 74 Liebert Series 610 SCC UPS - Input and HoldingData De

Strona 145

Modbus RTU and Modbus TCP Protocols - UPS Systems223 Liebert® IntelliSlot® Modbus/BACnetTable 75 Liebert HiPulse™, Liebert SICE 7200™- Input and Holdi

Strona 146

Modbus RTU and Modbus TCP Protocols - Thermal Management Products17 Liebert® IntelliSlot® Modbus/BACnetFan Speed 30103 — 1 — %1, 2, 3, 4, 5, 6, 7, 8,

Strona 147

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 224Rectifier Block — 40290 1 — Bit 7Rectifier Current Limit — 402

Strona 148 - 3.3 UPS Systems

Modbus RTU and Modbus TCP Protocols - UPS Systems225 Liebert® IntelliSlot® Modbus/BACnetTable 76 Liebert SICE 7200™ - Input and Holding - SSCControlle

Strona 149

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 226Output Undervoltage — 40290 1 — Bit 7Output Waveform Error — 4

Strona 150

Modbus RTU and Modbus TCP Protocols - UPS Systems227 Liebert® IntelliSlot® Modbus/BACnetTable 77 Liebert Npower™ - Input and Holding - IMPController S

Strona 151

Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 228Equipment Over Temperature — 40290 1 —Bit 0Any of Battery / He

Strona 152

Modbus RTU and Modbus TCP Protocols - Battery Monitoring Products229 Liebert® IntelliSlot® Modbus/BACnet3.4 Battery Monitoring ProductsTable 78 Alber®

Strona 153

Modbus RTU and Modbus TCP Protocols - Battery Monitoring ProductsLiebert® IntelliSlot® Modbus/BACnet 230Thermal Runaway Charger Current Level One Even

Strona 154 - Table 47 Liebert APS

Modbus RTU and Modbus TCP Protocols - Battery Monitoring Products231 Liebert® IntelliSlot® Modbus/BACnetTable 79 Alber® BDSU™ - Input and HoldingData

Strona 155 - - Input and Holding

Modbus RTU and Modbus TCP Protocols - Battery Monitoring ProductsLiebert® IntelliSlot® Modbus/BACnet 232Cell to Cell Temperature Deviation ThresholdSt

Strona 156 - Modbus/BACnet 150

Modbus RTU and Modbus TCP Protocols - Battery Monitoring Products233 Liebert® IntelliSlot® Modbus/BACnetCell Temperature Low Global ThresholdString 1

Strona 157 - 151 Liebert

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 18Return Humidity 30130 — 1 10 % RH1, 2, 3, 4, 5,

Strona 158 - Modbus/BACnet 152

Modbus RTU and Modbus TCP Protocols - Battery Monitoring ProductsLiebert® IntelliSlot® Modbus/BACnet 234Cell to Ambient Temperature Deviation Threshol

Strona 159 - 153 Liebert

Modbus RTU and Modbus TCP Protocols - Battery Monitoring Products235 Liebert® IntelliSlot® Modbus/BACnetCell TemperatureCell 321 – 36039195-39234 — 1

Strona 160 - - Glossary

BACnet Communications - BACnet Protocol Implementation Conformance StatementLiebert® IntelliSlot® Modbus/BACnet 2364.0 BACNET COMMUNICATIONS4.1 BACnet

Strona 161 - - Glossary (continued)

BACnet Communications - BACnet Protocol Implementation Conformance Statement237 Liebert® IntelliSlot® Modbus/BACnet4.1.2 Supported ServicesServiceOrig

Strona 162 - Modbus/BACnet 156

BACnet Communications - BACnet Protocol Implementation Conformance StatementLiebert® IntelliSlot® Modbus/BACnet 2384.1.3 Standard Object Types Support

Strona 163 - 157 Liebert

BACnet Communications - BACnet Protocol Implementation Conformance Statement239 Liebert® IntelliSlot® Modbus/BACnet4.1.4 Object PropertiesThe followin

Strona 164

BACnet Communications - BACnet Protocol Implementation Conformance StatementLiebert® IntelliSlot® Modbus/BACnet 240Analog ObjectUnitsPossible values o

Strona 165

BACnet Communications - BACnet Protocol Implementation Conformance Statement241 Liebert® IntelliSlot® Modbus/BACnetBinary Object PropertiesMultistate

Strona 166

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 2424.2 Thermal Management ProductsTable 80 Liebert Challenger 3

Strona 167 - - Status and Coil

BACnet Communications - Thermal Management Products243 Liebert® IntelliSlot® Modbus/BACnetCompressor Hours Exceeded Binary_Value 77 5269_1_1 RD Active

Strona 168 - Table 55 Liebert Nfinity

Modbus RTU and Modbus TCP Protocols - Thermal Management Products19 Liebert® IntelliSlot® Modbus/BACnetSupply Air Temperature Sensor Control30262 4026

Strona 169 - Table 56 Liebert NX

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 244Free Cooling Valve Hours ExceededBinary_Value 117 5306_1 RD

Strona 170 - 10264 — — — —

BACnet Communications - Thermal Management Products245 Liebert® IntelliSlot® Modbus/BACnetFanFan Hours Exceeded Binary_Value 205 5054_1 RD Active on A

Strona 171 - Table 57 Liebert NX

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 246High Power Shutdown Binary_Value 268 5121_1 RD Active on Ala

Strona 172 - Modbus/BACnet 166

BACnet Communications - Thermal Management Products247 Liebert® IntelliSlot® Modbus/BACnetSystem Events - iCOM DO Board 1Digital Output Board Not Dete

Strona 173 - 167 Liebert

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 248Remote Sensors - Remote Sensor 5Remote Sensor Over Temperatu

Strona 174 - (continued)

BACnet Communications - Thermal Management Products249 Liebert® IntelliSlot® Modbus/BACnetStatic PressureStatic Pressure Sensor Issue Binary_Value 563

Strona 175 - 169 Liebert

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 250Liebert Condensers (Previously called Global Condensers)Cond

Strona 176 - Table 59 Liebert NXL

BACnet Communications - Thermal Management Products251 Liebert® IntelliSlot® Modbus/BACnetCondenser Supply Refrigerant Under TempBinary_Value 1113 554

Strona 177 - 171 Liebert

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 252Table 82 Liebert Challenger 3000™, Liebert Challenger ITR™,

Strona 178 - Modbus/BACnet 172

BACnet Communications - Thermal Management Products253 Liebert® IntelliSlot® Modbus/BACnetAir - Return AirReturn Air Temperature Analog_Value 31 4291_

Strona 179 - Table 60 Liebert NXL

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 20Maintenance Tracking State 30286 — 1 —0 = off1

Strona 180 - Modbus/BACnet 174

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 254HumidityReturn Humidity Analog_Value 60 5028_1 RD Units: % R

Strona 181 - 175 Liebert

BACnet Communications - Thermal Management Products255 Liebert® IntelliSlot® Modbus/BACnetCompressors - Compressor 1Compressor Hours Analog_Value 97 5

Strona 182 - Modbus/BACnet 176

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 256Reheat - Electric Reheater 1Electric Reheater Hours Analog_V

Strona 183 - 177 Liebert

BACnet Communications - Thermal Management Products257 Liebert® IntelliSlot® Modbus/BACnetAnalog Inputs 3Analog Input Reading Analog_Value 246 5378_3

Strona 184 - Modbus/BACnet 178

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 258Dew Point Set Point Analog_Value 10295 5575_1_deg_F RW Units

Strona 185 - 179 Liebert

BACnet Communications - Thermal Management Products259 Liebert® IntelliSlot® Modbus/BACnetRemote Sensors - Remote Sensor 3Remote Sensor Temperature An

Strona 186 - Modbus/BACnet 180

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 260Pump Hours Analog_Value 526 5298_1_2 RW Units: hr 7, 8, 9Pow

Strona 187 - 181 Liebert

BACnet Communications - Thermal Management Products261 Liebert® IntelliSlot® Modbus/BACnetSystem Input RMS B-C Analog_Value 1922 4099_3 RD Units: VAC

Strona 188 - Modbus/BACnet 182

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 262System Input RMS B-C Analog_Value 1952 4099_6 RD Units: VAC

Strona 189 - 183 Liebert

BACnet Communications - Thermal Management Products263 Liebert® IntelliSlot® Modbus/BACnetCondenser Low Noise Mode - Full DaysAnalog_Value 534 5551_1_

Strona 190 - Modbus/BACnet 184

Modbus RTU and Modbus TCP Protocols - Thermal Management Products21 Liebert® IntelliSlot® Modbus/BACnetExt Loss of Flow - Event Type 30306 40306 1 —0

Strona 191 - Table 61 Liebert NXL

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 264Liebert Condensers - Condenser 2 Fan 2Condenser Fan Speed An

Strona 192 - Modbus/BACnet 186

BACnet Communications - Thermal Management Products265 Liebert® IntelliSlot® Modbus/BACnetTable 84 Liebert Challenger 3000™, Liebert Challenger ITR™,

Strona 193 - 187 Liebert

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 266FanFan Control Mode MultiState_Value 82 5373_1 RW1 = Auto2 =

Strona 194 - Modbus/BACnet 188

BACnet Communications - Thermal Management Products267 Liebert® IntelliSlot® Modbus/BACnetSystem Event ConfigurationCustomer Input 1 - Event ControlMu

Strona 195 - 189 Liebert

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 268Ext Over Temperature - Event ControlMultiState_Value 146 509

Strona 196 - Table 62 Liebert NXL

BACnet Communications - Thermal Management Products269 Liebert® IntelliSlot® Modbus/BACnetClogged Air Filter - Event ControlMultiState_Value 166 5135_

Strona 197 - 191 Liebert

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 270Compressor Low Suction Pressure - Event TypeMultiState_Value

Strona 198 - Modbus/BACnet 192

BACnet Communications - Thermal Management Products271 Liebert® IntelliSlot® Modbus/BACnetHigh Return Humidity - Event TypeMultiState_Value 235 5138_1

Strona 199 - 193 Liebert

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 272System EventsSystem Event Acknowledge/ResetMultiState_Value

Strona 200 - Modbus/BACnet 194

BACnet Communications - Thermal Management Products273 Liebert® IntelliSlot® Modbus/BACnetCold Aisle Force Max Fan/Cooling - Ext ControlMultiState_Val

Strona 201 - 195 Liebert

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 22Ext Compressor Lockout - Event Type30326 40326

Strona 202 - Modbus/BACnet 196

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 274Table 86 Liebert Challenger 3000™, Liebert Challenger ITR™,

Strona 203 - 197 Liebert

BACnet Communications - Thermal Management Products275 Liebert® IntelliSlot® Modbus/BACnetChilled Water Control Valve FailureChilled water valve out o

Strona 204 - Modbus/BACnet 198

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 276Compressor HoursOperating hours for compressor since last re

Strona 205 - 199 Liebert

BACnet Communications - Thermal Management Products277 Liebert® IntelliSlot® Modbus/BACnetCondenser Issue - Event Type The event type for the [Condens

Strona 206 - Modbus/BACnet 200

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 278Cooling Control TemperatureTemperature value being used for

Strona 207 - 201 Liebert

BACnet Communications - Thermal Management Products279 Liebert® IntelliSlot® Modbus/BACnetDigital Scroll Compressor LoadingPresent digital scroll comp

Strona 208 - Modbus/BACnet 202

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 280Ext Air Sensor A Under Temp - Event ControlEnable/disable th

Strona 209 - 203 Liebert

BACnet Communications - Thermal Management Products281 Liebert® IntelliSlot® Modbus/BACnetExt Loss of Air Blower Loss of air blower is detected, as in

Strona 210 - Table 64 Liebert NXL

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 282Fan Issue - Event ControlEnable/disable the activation of th

Strona 211 - 205 Liebert

BACnet Communications - Thermal Management Products283 Liebert® IntelliSlot® Modbus/BACnetHigh Return Humidity - Event ControlEnable/disable the activ

Strona 212 - Modbus/BACnet 206

Modbus RTU and Modbus TCP Protocols - Thermal Management Products23 Liebert® IntelliSlot® Modbus/BACnetCompressor Short Cycle - Event Type 230346 4034

Strona 213 - 207 Liebert

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 284Humidity Proportional Control TypeType of algorithm to use f

Strona 214 - Modbus/BACnet 208

BACnet Communications - Thermal Management Products285 Liebert® IntelliSlot® Modbus/BACnetPump State Pump operational state.Pump Unspecified General E

Strona 215 - 209 Liebert

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 286Return Air Under Temp - Event ControlEnable/disable the acti

Strona 216 - Modbus/BACnet 210

BACnet Communications - Thermal Management Products287 Liebert® IntelliSlot® Modbus/BACnetSupply Air Under Temp ThresholdThreshold value used in the [

Strona 217 - 211 Liebert

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 288Unit Partial Shutdown An event has occurred requiring some s

Strona 218 - Table 65 Liebert PowerSure

BACnet Communications - Thermal Management Products289 Liebert® IntelliSlot® Modbus/BACnetTable 87 Liebert CRV™ - Binary DataController Liebert iCOM®

Strona 219 - Table 66 Liebert PowerSure

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 290Remote Sensors 10Remote Sensor Issue Binary_Value 151 5060_1

Strona 220 - Table 67 Liebert PowerSure

BACnet Communications - Thermal Management Products291 Liebert® IntelliSlot® Modbus/BACnetUnit Partial Shutdown Binary_Value 237 5112_1 RD Active on A

Strona 221 - 215 Liebert

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 292Table 88 Liebert CRV™ - Analog DataController Liebert iCOM®

Strona 222 - UPS - Status and Coil

BACnet Communications - Thermal Management Products293 Liebert® IntelliSlot® Modbus/BACnetRemote Sensors 1Remote Sensor Temperature Analog_Value 56 5

Strona 223 - UPS - Input and Holding

iTABLE OF CONTENTS1.0 LIEBERT EQUIPMENT COMPATIBILITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11.1 What’s Ne

Strona 224 - Modbus/BACnet 218

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 24Low Return Humidity - Event Type 30366 40366 1

Strona 225 - Table 71 Liebert Series 600

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 294 Condenser Low Noise Mode - Interval Days Analog_Value 287

Strona 226 - Table 72 Liebert Series 600

BACnet Communications - Thermal Management Products295 Liebert® IntelliSlot® Modbus/BACnetTable 89 Liebert CRV™ - Multistate DataController Liebert iC

Strona 227 - SCC UPS - Status and Coil

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 296Event ConfigurationSystem Event Acknowledge/Reset MultiStat

Strona 228 - Modbus/BACnet 222

BACnet Communications - Thermal Management Products297 Liebert® IntelliSlot® Modbus/BACnetExt Reheat Lockout - Event Type MultiState_Value 191 5085_1

Strona 229

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 298Table 90 Liebert CRV™ - GlossaryData Label Data DescriptionA

Strona 230

BACnet Communications - Thermal Management Products299 Liebert® IntelliSlot® Modbus/BACnetCondenser Low Noise Mode Stop Time The time of day at which

Strona 231 - - Input and Holding - SSC

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 300Customer Input 3 - Event Type The event type for the [Custo

Strona 232 - Modbus/BACnet 226

BACnet Communications - Thermal Management Products301 Liebert® IntelliSlot® Modbus/BACnetFan Hours Exceeded Operating hours for the unit blower fan

Strona 233 - - Input and Holding - IMP

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 302Remote Sensor Temperature Calculation Calculation method app

Strona 234 - Modbus/BACnet 228

BACnet Communications - Thermal Management Products303 Liebert® IntelliSlot® Modbus/BACnetSystem Operating State Current operating state of the syste

Strona 235

Modbus RTU and Modbus TCP Protocols - Thermal Management Products25 Liebert® IntelliSlot® Modbus/BACnetOutside Air Temperature 30484 — 1 10 deg C2, 3,

Strona 236

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 304Table 91 Liebert HPC™ - Binary DataController Liebert iCOM®

Strona 237

BACnet Communications - Thermal Management Products305 Liebert® IntelliSlot® Modbus/BACnetFluid - Supply (Outlet) FluidSupply Fluid Over Temp Binary_V

Strona 238

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 306Table 92 Liebert HPC™ - Analog DataController Liebert iCOM®

Strona 239

BACnet Communications - Thermal Management Products307 Liebert® IntelliSlot® Modbus/BACnetFree CoolingFree Cooling External Temperature Delta Analog_V

Strona 240

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 308Table 93 Liebert HPC™ - Multistate DataController Liebert iC

Strona 241

BACnet Communications - Thermal Management Products309 Liebert® IntelliSlot® Modbus/BACnetTable 94 Extra NotesNumber Description1This point is support

Strona 242 - 4.0 BACNET COMMUNICATIONS

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 310Customer Input 1 Customer input 1.Customer Input 2 Customer

Strona 243 - 4.1.2 Supported Services

BACnet Communications - Thermal Management Products311 Liebert® IntelliSlot® Modbus/BACnetPump Hours Threshold Threshold value used in the [Pump Hours

Strona 244 - Modbus/BACnet 238

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 312Table 96 Liebert XDP™, Liebert XDC™ - Binary DataController

Strona 245 - Device Object

BACnet Communications - Thermal Management Products313 Liebert® IntelliSlot® Modbus/BACnetXD System 1Ext System Condensation Detected Binary_Value 112

Strona 246 - Analog Object

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 26Actual Humidity Set Point 30502 — 1 — % RH2, 3,

Strona 247 - Multistate Object Properties

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 314Table 97 Liebert XDP™, Liebert XDC™ - Analog DataController

Strona 248

BACnet Communications - Thermal Management Products315 Liebert® IntelliSlot® Modbus/BACnetXD System 1 Temperature Sensor 4Remote Sensor Temperature An

Strona 249

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 316Table 98 Liebert XDP™, Liebert XDC™ - Multistate DataControl

Strona 250

BACnet Communications - Thermal Management Products317 Liebert® IntelliSlot® Modbus/BACnetRefrigerantSupply Refrig Over Temp - Event Control Multistat

Strona 251

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 318CompressorsCompressor 1A State Multistate_Value 91 4665_1 RD

Strona 252

BACnet Communications - Thermal Management Products319 Liebert® IntelliSlot® Modbus/BACnetCircuit 2 Low Suction Pressure - EventTypeMultistate_Value 1

Strona 253

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 320Fan Button Control Multistate_Value 175 5488_2 RW1 = Enabled

Strona 254

BACnet Communications - Thermal Management Products321 Liebert® IntelliSlot® Modbus/BACnetSensor Issue - Event Type Multistate_Value 812 5499_20 RW1 =

Strona 255

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 322Smoke Detected - Event Type Multistate_Value 859 4722_1 RW1

Strona 256

BACnet Communications - Thermal Management Products323 Liebert® IntelliSlot® Modbus/BACnetCold Aisle Temp Out of RangeThe air temperature in the cold

Strona 257

Modbus RTU and Modbus TCP Protocols - Thermal Management Products27 Liebert® IntelliSlot® Modbus/BACnetRemote Sensor Temperature 5 30555 — 1 10 deg C2

Strona 258

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 324Compressor 2B Short Cycle - Event ControlEnable/disable the

Strona 259

BACnet Communications - Thermal Management Products325 Liebert® IntelliSlot® Modbus/BACnetExt Air Sensor B Temperature Air temperature as measured by

Strona 260

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 326Hot Gas Valve 2 Open Position Hot gas valve 2 open position.

Strona 261

BACnet Communications - Thermal Management Products327 Liebert® IntelliSlot® Modbus/BACnetShutdown - Loss Of PowerSystem lost power. This event become

Strona 262

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 328Supply Refrig Temp Sensor Issue - Event TypeThe event type f

Strona 263

BACnet Communications - Thermal Management Products329 Liebert® IntelliSlot® Modbus/BACnetTable 100 Liebert DataMate™, Liebert Mini-Mate2™ - MM2Contro

Strona 264

BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 330Table 101 Liebert Mini-Mate2™ 8 Ton - L8TController L8TLiebe

Strona 265

BACnet Communications - UPS Systems331 Liebert® IntelliSlot® Modbus/BACnet4.3 UPS SystemsTable 102 Liebert APM™, Liebert NXC™, Liebert NXR™ - Binary D

Strona 266

BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 332Power Sub Module Fault Binary_Value 51 5158_1 RD Active on AlarmBattery Disc

Strona 267

BACnet Communications - UPS Systems333 Liebert® IntelliSlot® Modbus/BACnetSystem Output RMS Current Phs B Analog_Value 57 4205_1 RD Units: A AC Syste

Strona 268

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 28Digital Scroll Compressor Loading 2 30669 — 1 —

Strona 269

BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 334Table 105 Liebert APM™, Liebert NXC™, Liebert NXR™ - GlossaryData Label Data

Strona 270

BACnet Communications - UPS Systems335 Liebert® IntelliSlot® Modbus/BACnetLoad Sharing Fault Difference between any phase inverter current of unit and

Strona 271

BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 336System Output Pct Power Phase B The system output power on phase B as a perc

Strona 272

BACnet Communications - UPS Systems337 Liebert® IntelliSlot® Modbus/BACnetTable 106 Liebert APS™ - Binary DataData LabelObject Type InstanceObjectName

Strona 273

BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 338PowerModule 1Power Module Fan Fault Binary_Value 99 5838_1 RD Active on Ala

Strona 274

BACnet Communications - UPS Systems339 Liebert® IntelliSlot® Modbus/BACnetTable 107 Liebert APS™ - Analog DataData LabelObject Type Instance Object Na

Strona 275

BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 340System Output Apparent Power L2 Analog_Value 71 5869_1 RD Units: kVA System

Strona 276

BACnet Communications - UPS Systems341 Liebert® IntelliSlot® Modbus/BACnetTable 108 Liebert APS™ - Multistate DataData LabelObject Type Instance Objec

Strona 277

BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 342Auto Restart Minimum Battery Setting MultiState_Value 64 5832_1 RW1 = 0%2 =

Strona 278

BACnet Communications - UPS Systems343 Liebert® IntelliSlot® Modbus/BACnetTable 109 Liebert APS™ - GlossaryData Label Data DescriptionAccumulated Disc

Strona 279

Modbus RTU and Modbus TCP Protocols - Thermal Management Products29 Liebert® IntelliSlot® Modbus/BACnetSystem Input RMS C-N 3 30822 — 1 10 VAC 5System

Strona 280

BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 344DC Bus Current The current at the battery input terminals. In charging mode,

Strona 281

BACnet Communications - UPS Systems345 Liebert® IntelliSlot® Modbus/BACnetOutput Load on Maint. Bypass The output power is supplied by the maintenanc

Strona 282

BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 346System Output Off The system output is off System Output Pct Power L1 The s

Strona 283

BACnet Communications - UPS Systems347 Liebert® IntelliSlot® Modbus/BACnetTable 110 Liebert NXL™- 60Hz, UL version (Model 40) - Binary DataData LabelO

Strona 284

BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 348Battery Self Test Binary_Value 46 4741_1 RD Active on AlarmSMS, 1+N, N+1Mai

Strona 285

BACnet Communications - UPS Systems349 Liebert® IntelliSlot® Modbus/BACnetOutput Amp Over User Limit-Phs A Binary_Value 91 4286_1 RD Active on AlarmS

Strona 286

BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 350Input Contact 09 Binary_Value 146 4278_1 RD Active on AlarmSMS, 1+N, N+1, S

Strona 287

BACnet Communications - UPS Systems351 Liebert® IntelliSlot® Modbus/BACnetInput Filter Cycle Lock Binary_Value 192 4755_1 RD Active on AlarmSMS, 1+N,

Strona 288

BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 352Table 111 Liebert NXL™ - 60Hz, UL version (Model 40) - Analog DataData Label

Strona 289

BACnet Communications - UPS Systems353 Liebert® IntelliSlot® Modbus/BACnetBattery Volts for Cabinet 8 Analog_Value 45 4155_1_8 RD Units: VDCSMS, 1+N,

Strona 290

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 30Fluid Input Temperature 2 30901 — 1 10 deg C 5F

Strona 291

BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 354DC BusDC Bus Voltage Analog_Value 72 4148_1 RD Units: VDCSMS, 1+N, N+1DC Bu

Strona 292

BACnet Communications - UPS Systems355 Liebert® IntelliSlot® Modbus/BACnetEnvironmentInlet Air Temperature Analog_Value 126 4291_1 RD Units: deg CSMS

Strona 293

BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 356MultiModuleMulti-module System Output Voltage RMS A-B Analog_Value 177 4801_

Strona 294

BACnet Communications - UPS Systems357 Liebert® IntelliSlot® Modbus/BACnet ModuleList 2MMS Module Total kW Output Analog_Value 226 4861_2 RD Units: k

Strona 295 - - Binary Data

BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 358Table 112 Liebert NXL™ - 60Hz, UL version (Model 40) - Multistate DataData L

Strona 296 - - Binary Data (continued)

BACnet Communications - UPS Systems359 Liebert® IntelliSlot® Modbus/BACnetSystemUPS Module Type MultiState_Value 84 4303_1 RD1 = Single ModuleSystem2

Strona 297 - 291 Liebert

BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 360System Status MultiState_Value 91 4123_1 RD1 = Normal Operation2 = StartUp 3

Strona 298 - - Analog Data

BACnet Communications - UPS Systems361 Liebert® IntelliSlot® Modbus/BACnetMultiModuleModule Output Breaker for Module 1 (MOB1) MultiState_Value 137 48

Strona 299 - - Analog Data (continued)

BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 362SCC Event Summary MultiState_Value 156 4855_1 RD1 = None2 = Alarm3 = Fault

Strona 300

BACnet Communications - UPS Systems363 Liebert® IntelliSlot® Modbus/BACnetMMS Module Output Voltage Status MultiState_Value 277 4859_8 RD1 = Fail2 = M

Strona 301 - - Multistate Data

Modbus RTU and Modbus TCP Protocols - Thermal Management Products31 Liebert® IntelliSlot® Modbus/BACnetPump State 2 31110 — 1 —0 = off1 = on8, 9Expect

Strona 302 - Modbus/BACnet 296

BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 364Table 113 Liebert NXL™ - 60Hz, UL version (Model 40) - GlossaryData Label Da

Strona 303 - 297 Liebert

BACnet Communications - UPS Systems365 Liebert® IntelliSlot® Modbus/BACnetBattery Time Remaining The calculated available time on battery Battery Tot

Strona 304 - Table 90 Liebert CRV

BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 366Continuous Operation - ECO Mode This setting gives the user the ability to E

Strona 305 - 299 Liebert

BACnet Communications - UPS Systems367 Liebert® IntelliSlot® Modbus/BACnetIntelligent Parallel Minimum Redundancy This is the minimum Number of Redund

Strona 306 - Modbus/BACnet 300

BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 368MMS Module DC Bus Voltage DC bus voltage of this module in a multi-module s

Strona 307 - 301 Liebert

BACnet Communications - UPS Systems369 Liebert® IntelliSlot® Modbus/BACnetMulti-module System Output Voltage RMS A-N Multi-module system output RMS v

Strona 308 - Modbus/BACnet 302

BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 370SCC Event Summary Summary of any active user alarms or faults on the SCC Sc

Strona 309 - 303 Liebert

BACnet Communications - UPS Systems371 Liebert® IntelliSlot® Modbus/BACnetSystem Output Frequency The system output frequency System Output Low Power

Strona 310 - Table 91 Liebert HPC

BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 372Table 114 Liebert NXL™ - 50 Hz, CE version (Models 48 and 49)—Binary DataDat

Strona 311 - 305 Liebert

BACnet Communications - UPS Systems373 Liebert® IntelliSlot® Modbus/BACnetDC BusDC Bus Low Fault Binary_Value 74 5563_1 RD Active on AlarmOutputSystem

Strona 312 - Table 92 Liebert HPC

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 32Table 9 Extra notes key to Table 8NumberDescrip

Strona 313 - 307 Liebert

BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 374SystemSystem Fan Failure - Redundant Binary_Value 174 4749_1 RD Active on Al

Strona 314 - Table 93 Liebert HPC

BACnet Communications - UPS Systems375 Liebert® IntelliSlot® Modbus/BACnetIntelligent ParallelingIP Inhibit Binary_Value 251 5567_1 RD Active on Alarm

Strona 315

BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 376Table 115 Liebert NXL™ - 50 Hz, CE version (Models 48 and 49)—Analog DataDat

Strona 316 - Table 95 Liebert HPC

BACnet Communications - UPS Systems377 Liebert® IntelliSlot® Modbus/BACnetDC BusDC Bus Voltage Analog_Value 66 4148_1 RD Units: VDCDC Bus Current Anal

Strona 317 - 311 Liebert

BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 378MultiModuleMulti-module System Output Voltage RMS A-B Analog_Value 155 4801_

Strona 318

BACnet Communications - UPS Systems379 Liebert® IntelliSlot® Modbus/BACnetTable 116 Liebert NXL™ - 50 Hz, CE version (Models 48 and 49)—Multistate Dat

Strona 319

BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 380SystemUPS Module Type MultiState_Value 87 4303_1 RD1 = Single Module System2

Strona 320

BACnet Communications - UPS Systems381 Liebert® IntelliSlot® Modbus/BACnetConfiguration Description MultiState_Value 91 4751_1 RD1 = Single Module Sys

Strona 321

BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 382RatingsInput Isolation Transformer MultiState_Value 109 4266_1 RD1 = Not Ins

Strona 322

BACnet Communications - UPS Systems383 Liebert® IntelliSlot® Modbus/BACnetModule Output Breaker for Module 7 MultiState_Value 147 4842_1 RD1 = Open2 =

Strona 323

Modbus RTU and Modbus TCP Protocols - Thermal Management Products33 Liebert® IntelliSlot® Modbus/BACnetTable 10 Liebert Challenger 3000™, Liebert Chal

Strona 324

BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 384ModuleList 1MMS Inter-Module Comm Status MultiState_Value 173 4856_1 RD1 = F

Strona 325

BACnet Communications - UPS Systems385 Liebert® IntelliSlot® Modbus/BACnetECO ModeECO Mode Operation State MultiState_Value 304 5454_1 RW1 = disabled2

Strona 326

BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 386Table 117 Liebert NXL™ - 50 Hz, CE version (Models 48 and 49)—GlossaryData L

Strona 327

BACnet Communications - UPS Systems387 Liebert® IntelliSlot® Modbus/BACnetBattery Volts at Main DisconnectThe voltage between the positive and the neg

Strona 328

BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 388ECO Mode Operation State This setting is used to enable or disable ECO Mode.

Strona 329

BACnet Communications - UPS Systems389 Liebert® IntelliSlot® Modbus/BACnetInverter Overload Phase C Inverter is operating with an overload on phase CI

Strona 330

BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 390MMS Output Power The sum total power of all system output modulesMMS Overloa

Strona 331

BACnet Communications - UPS Systems391 Liebert® IntelliSlot® Modbus/BACnetProgram Input Contact 03When the signal from [Program Input Contact 03] is a

Strona 332

BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 392Sum of MMS Output RMS Currents for Phase AThe sum of the multi-module system

Strona 333

BACnet Communications - UPS Systems393 Liebert® IntelliSlot® Modbus/BACnetSystem Output Pct Pwr (VA) Phs BThe system output apparent power on phase B

Strona 334

iiTable 18 Liebert XDC™ - Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67Table 19 Liebe

Strona 335

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 34BMS Timeout PeriodTimeframe within which the Bu

Strona 336 - 8 Ton - L8T

While every precaution has been taken to ensure the accuracyand completeness of this literature, Liebert Corporation assumes noresponsibility and disc

Strona 337 - 4.3 UPS Systems

Modbus RTU and Modbus TCP Protocols - Thermal Management Products35 Liebert® IntelliSlot® Modbus/BACnetCompressor High Pressure Transducer IssueCompre

Strona 338

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 36Condenser Fan Reversal Requested Request the co

Strona 339

Modbus RTU and Modbus TCP Protocols - Thermal Management Products37 Liebert® IntelliSlot® Modbus/BACnetCooling Control TemperatureTemperature value be

Strona 340

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 38Dig Scroll Comp Over TempDigital scroll compres

Strona 341

Modbus RTU and Modbus TCP Protocols - Thermal Management Products39 Liebert® IntelliSlot® Modbus/BACnetExt Air Sensor A Over Temp - Event TypeThe even

Strona 342

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 40Ext Humidifier Lockout - Event ControlEnable/di

Strona 343 - Table 106 Liebert APS

Modbus RTU and Modbus TCP Protocols - Thermal Management Products41 Liebert® IntelliSlot® Modbus/BACnetExternal Condenser TVSS IssueThe condenser Tran

Strona 344 - Modbus/BACnet 338

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 42Free Cooling Internal Temperature DeltaMinimum

Strona 345 - Analog Data

Modbus RTU and Modbus TCP Protocols - Thermal Management Products43 Liebert® IntelliSlot® Modbus/BACnetHumidifier Issue - Event ControlEnable/disable

Strona 346 - Analog Data (continued)

iiiTable 52 Liebert HiNet™ - Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160Table 53 Liebe

Strona 347

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 44Main Fan Overload Main fan is shut down due to

Strona 348 - Table 108 Liebert APS

Modbus RTU and Modbus TCP Protocols - Thermal Management Products45 Liebert® IntelliSlot® Modbus/BACnetRemote Sensor System Average TemperatureAverage

Strona 349 - Table 109 Liebert APS

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 46Shutdown - Loss Of Power - Event Type The event

Strona 350 - Modbus/BACnet 344

Modbus RTU and Modbus TCP Protocols - Thermal Management Products47 Liebert® IntelliSlot® Modbus/BACnetSystem Operating State Current operating state

Strona 351 - 345 Liebert

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 48Table 11 Liebert CRV™ - Status and CoilControll

Strona 352 - Modbus/BACnet 346

Modbus RTU and Modbus TCP Protocols - Thermal Management Products49 Liebert® IntelliSlot® Modbus/BACnetSupply Chilled Water Over Temp 10047 — 1 — Acti

Strona 353 - Table 110 Liebert NXL

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 50Table 12 Liebert CRV™ - Input and HoldingContro

Strona 354 - Modbus/BACnet 348

Modbus RTU and Modbus TCP Protocols - Thermal Management Products51 Liebert® IntelliSlot® Modbus/BACnetRemote Sensor Temperature Module Index 4 30427

Strona 355 - 349 Liebert

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 52Fan Control Sensor 30463 40463 1 —0 = Supply1 =

Strona 356 - Modbus/BACnet 350

Modbus RTU and Modbus TCP Protocols - Thermal Management Products53 Liebert® IntelliSlot® Modbus/BACnetCondenser Low Noise Mode Schedule Control 3049

Strona 357 - 351 Liebert

ivTable 82 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert DeluxeSystem/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert P

Strona 358 - Table 111 Liebert NXL

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 54Table 13 Liebert CRV™ - GlossaryController Lieb

Strona 359 - 353 Liebert

Modbus RTU and Modbus TCP Protocols - Thermal Management Products55 Liebert® IntelliSlot® Modbus/BACnetCondenser Refrigerant Pressure Over Threshold C

Strona 360 - Modbus/BACnet 354

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 56Fan Speed Proportional Band Temperature control

Strona 361 - 355 Liebert

Modbus RTU and Modbus TCP Protocols - Thermal Management Products57 Liebert® IntelliSlot® Modbus/BACnetReturn Air Over Temp Threshold Threshold value

Strona 362 - Modbus/BACnet 356

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 58Table 14 Liebert HPC™ (Chiller) - Status and Co

Strona 363

Modbus RTU and Modbus TCP Protocols - Thermal Management Products59 Liebert® IntelliSlot® Modbus/BACnetFluidLow Fluid Pressure 10070 — 1 Active on Ala

Strona 364 - Table 112 Liebert NXL

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 60Table 15 Liebert HPC™ (Chiller) - Input and Hol

Strona 365 - 359 Liebert

Modbus RTU and Modbus TCP Protocols - Thermal Management Products61 Liebert® IntelliSlot® Modbus/BACnetCondensers 4Condenser Fan Speed 30417 — 1 —Unit

Strona 366 - Modbus/BACnet 360

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 62EvaporatorsEvaporator Return Fluid Temperature

Strona 367 - 361 Liebert

Modbus RTU and Modbus TCP Protocols - Thermal Management Products63 Liebert® IntelliSlot® Modbus/BACnetSystem OperationsReturn Fluid Temperature 30491

Strona 368 - Modbus/BACnet 362

Liebert Equipment Compatibility - What’s New in This Manual1Liebert® IntelliSlot® Modbus/BACnet1.0 LIEBERT EQUIPMENT COMPATIBILITY1.1 What’s New in Th

Strona 369 - 363 Liebert

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 64Table 16 Extra notes key to Table 15NumberDescr

Strona 370 - Table 113 Liebert NXL

Modbus RTU and Modbus TCP Protocols - Thermal Management Products65 Liebert® IntelliSlot® Modbus/BACnetEvaporator Fluid Freeze - Auto ResetEvaporator

Strona 371 - 365 Liebert

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 66Reheat UtilizationPresent reheating utilization

Strona 372 - Modbus/BACnet 366

Modbus RTU and Modbus TCP Protocols - Thermal Management Products67 Liebert® IntelliSlot® Modbus/BACnetTable 18 Liebert XDC™ - Status and CoilControll

Strona 373 - 367 Liebert

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 68Table 19 Liebert XDC™ - Input and HoldingContro

Strona 374 - Modbus/BACnet 368

Modbus RTU and Modbus TCP Protocols - Thermal Management Products69 Liebert® IntelliSlot® Modbus/BACnetSystem Status 30422 — 1 —1 = Normal Operation2

Strona 375 - 369 Liebert

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 70Table 20 Liebert XDP™ - Status and CoilControll

Strona 376 - Modbus/BACnet 370

Modbus RTU and Modbus TCP Protocols - Thermal Management Products71 Liebert® IntelliSlot® Modbus/BACnetXD System 2Ext System Condensation Detected 100

Strona 377 - 371 Liebert

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 72Table 21 Liebert XDP™ - Input and HoldingContro

Strona 378 - Table 114 Liebert NXL

Modbus RTU and Modbus TCP Protocols - Thermal Management Products73 Liebert® IntelliSlot® Modbus/BACnetExt Air Sensor B Dew Point Temp 30402 — 1 10 Un

Strona 379 - 373 Liebert

Liebert Equipment Compatibility - Compatibility with Liebert EquipmentLiebert® IntelliSlot® Modbus/BACnet 21.3 Compatibility with Liebert EquipmentTab

Strona 380 - Modbus/BACnet 374

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 74Ext Remote Shutdown - Event Type 30458 40458 1

Strona 381 - 375 Liebert

Modbus RTU and Modbus TCP Protocols - Thermal Management Products75 Liebert® IntelliSlot® Modbus/BACnetCold Aisle Under Temp Threshold 30493 40493 1 —

Strona 382 - Table 115 Liebert NXL

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 76XD System 1 Temperature Sensor 4Remote Sensor T

Strona 383 - 377 Liebert

Modbus RTU and Modbus TCP Protocols - Thermal Management Products77 Liebert® IntelliSlot® Modbus/BACnetXD System 4 Temperature Sensor 4Remote Sensor T

Strona 384 - Modbus/BACnet 378

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 78XD System 7 Temperature Sensor 4Remote Sensor T

Strona 385 - Table 116 Liebert NXL

Modbus RTU and Modbus TCP Protocols - Thermal Management Products79 Liebert® IntelliSlot® Modbus/BACnetXD System 10 Temperature Sensor 4Remote Sensor

Strona 386 - Modbus/BACnet 380

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 80XD System 13 Temperature Sensor 4Remote Sensor

Strona 387 - 381 Liebert

Modbus RTU and Modbus TCP Protocols - Thermal Management Products81 Liebert® IntelliSlot® Modbus/BACnetXD System 16 Temperature Sensor 4Remote Sensor

Strona 388 - Modbus/BACnet 382

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 82XD System 19 Temperature Sensor 4Remote Sensor

Strona 389 - 383 Liebert

Modbus RTU and Modbus TCP Protocols - Thermal Management Products83 Liebert® IntelliSlot® Modbus/BACnetTable 22 Liebert XDP™ - GlossaryController Lieb

Strona 390 - Modbus/BACnet 384

Liebert Equipment Compatibility - Compatibility with Liebert Equipment3Liebert® IntelliSlot® Modbus/BACnet• Power Distribution & Power Conditionin

Strona 391 - 385 Liebert

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 84Ext Remote Shutdown Unit is shut down by a remo

Strona 392 - Table 117 Liebert NXL

Modbus RTU and Modbus TCP Protocols - Thermal Management Products85 Liebert® IntelliSlot® Modbus/BACnetSmoke Detected Smoke detected.Supply Chilled Wa

Strona 393 - 387 Liebert

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 86Table 23 Liebert DS™ and Liebert PeX™ - Status

Strona 394 - Modbus/BACnet 388

Modbus RTU and Modbus TCP Protocols - Thermal Management Products87 Liebert® IntelliSlot® Modbus/BACnetComp 1 Overload 10039 — 1 — —Comp 1 Pumpdown Fa

Strona 395 - 389 Liebert

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 88HW/HG Hrs Exceeded 10087 — 1 — —Hum Hrs Exceed

Strona 396 - Modbus/BACnet 390

Modbus RTU and Modbus TCP Protocols - Thermal Management Products89 Liebert® IntelliSlot® Modbus/BACnetTable 24 Liebert DS™ and Liebert PeX™ - Input a

Strona 397 - 391 Liebert

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 90Electrical Heaters #1 Run Hours Threshold 3007

Strona 398 - Modbus/BACnet 392

Modbus RTU and Modbus TCP Protocols - Thermal Management Products91 Liebert® IntelliSlot® Modbus/BACnetDaily Low Temp Time 30154 — — — Hh:mmDaily High

Strona 399 - 393 Liebert

Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 92Table 25 Liebert XDF™ - Status and CoilControll

Strona 400 - Locations

Modbus RTU and Modbus TCP Protocols - Thermal Management Products93 Liebert® IntelliSlot® Modbus/BACnetTable 26 Liebert XDF™ - Input and HoldingContro