Przeglądanie stron 208
Modbus RTU and Modbus TCP Protocols - UPS Systems
203 Liebert
®
IntelliSlot
®
Modbus/BACnet
EcoModeSchedule 14
Schedule Operation State - ECO Mode 31019 1
0 = disabled
1 = enabled
Schedule Action - ECO Mode 31020 1
0 = stop
1 = start
Schedule Day of Week - ECO Mode 31021 1
0 = Unknown
1 = Monday
2 = Tuesday
3 = Wednesday
4 = Thursday
5 = Friday
6 = Saturday
7 = Sunday
Schedule Hour - ECO Mode 31022 1
Units : hr
Uint16
Schedule Minute - ECO Mode 31023 1
Units : min
Uint16
Table 63 Liebert NXL™ - 50Hz, CE version (Models 48 and 49) - Input and Holding (continued)
Data Label
Input Holding # of Reg Scale Notes/Units